TWO INCH DEFLECTION SPRING ISOLATOR INSTALLATION
Installation Instructions
1.Read instructions in their entirety before beginning
installation.
2.Isolators are shipped fully assembled. Make sure the AVM
types are correct (print codes and adhesive labels) and match
each load point with corresponding isolators.
3.Twist off the fixing bolt and washer anticlockwise.
4.Set isolators on floor. Ensure that all isolator centerlines match
the equipment mounting holes. The isolator base be installed on
a level surface. Leveling all isolator bases to the same elevation
(1/4-inch maximum difference can be tolerated).
5.Place equipment on top of isolators making sure that mounting
holes of the equipment line up with isolator installation holes.
Load label
550
550
B olt
JOHNSON CONTROLS
Cooke Industries - Phone: +64 9 579 2185
AND ADJUSTMENT
F ixing bolt
Washer
550
Step 1
Unit
R uler
550
L evel basement
Step 4
Email: sales@cookeindustries.co.nz
SECTION 5 – TECHNICAL DATA
6.Place the fixing bolt and washer but do not tighten them.
7.Ensure the verticality of the isolators and use bolts to fix the
bases of the isolators to the level floor. Use the same torque to
fasten the bolts.
8.The adjustment process can only begin after the equipment or
machine is at its full operating weight.
9.Measure the height of the housing. Adjust each isolator in
sequence by turning adjusting bolt. Repeat this procedure on all
isolators, one at a time.
10.Fine adjust isolators to level equipment. Fasten the nut and
fixing bolt.
11.Installation is complete.
A djusting
Unit
bolt
Step 2
Adjusting
bolt
L evel basement
Step 5
Web: www.cookeindustries.co.nz
F ixing
bolt
550
Step 3
Lo ck
F ixing
bolt
550
Step 6