1.Pressure Drop is the total water resistance across BPHE and water piping;
2.In Correlations, x represents Flow Rate in L/s, and y represents Pressure Drop in kPa.
JOHNSON CONTROLS
Cooke Industries - Phone: +64 9 579 2185

OPERATIONAL LIMITATIONS

OPERATIONAL LIMITATIONS
HEAT EXCHANGER PRESSURE DROP
HEAT EXCHANGER PRESSURE DROP
PRESSURE
DROP CURVE
A
y = 1.4169*x^3 - 2.7902*x^2 + 18.488*x - 9.0295
B
y = 0.1071*x^3 + 1.3526*x^2 + 4.525*x - 3.4853
C
y = -0.1316*x^3 + 3.4848*x^2 - 6.0541*x + 7.4083
D
y = -0.1233*x^3 + 2.6949*x^2 - 4.8171*x + 5.4692
E
y = -0.0589*x^3 + 1.8285*x^2 - 3.8203*x + 6.6512
F
y = 0.0117*x^3 + 0.0583*x^2 + 2.7108*x - 5.8985
G
y = -0.0041*x^3 + 0.4305*x^2 - 0.4644*x + 2.9758
H
y = 0.0065*x^3 + 0.0985*x^2 + 2.5877*x - 7.5858
I
y = 0.0004*x^3 + 0.2096*x^2 + 0.5379*x - 1.1606
FIGURE 25 – HEAT EXCHANGER PRESSURE DROP CURVE