System Configuration

For Mass Notification Systems (UL2572) and Fire Evacuation Systems (UL864) the following
minimum and optional configurations are allowed.
This section covers the configurations needed to meet the intended applications. The
minimum (M) and optional (O) required products are included.
Order number
Product name
PRA-SCL
System controller,
large
PRA-AD604
Amplifier, 600W
4‑channel
PRA-AD608
Amplifier, 600W 8-
channel
PRA-MPS3
Multifunction power
supply, large
PRA-CSLD
Desktop LCD call
station
PRA-CSLW
Wallmount LCD call
station
PRA-FRPx‑US
First responder panel
USA, 3‑extensions
PRA‑EOL‑US
End-of-line device
PRA-CSE
Call station extension
PRA-ES8P2S
Ethernet switch
PRA-SFPLX
Fiber Transceiver single
mode
PRA-SFPSX
Fiber Transceiver multi-
mode
Refer to
Bosch Security Systems B.V.
Mandatory /
Optional
M
O* (or PRA-
AD608)
O* (or PRA-
AD604)
M
O
O
M
M
M
O
O
O
O*: Non, or at least one of the (and/or) described product is required.
Interconnection with B9512G or B8512G panel, page 153
Underwriters Laboratories Listing Document (ULLD)
Minimum
Maximum per system / product
quantity
1
Per system: 3
O*
O*
1
0
0
Per system: 150 - # of PRA-SCL and
PRA‑FRPx‑US
1
Per system: 20
1
Per amplifier output A: 1
Per amplifier output B: 1
1
Per PRA-CSLx: 4
0
Per PRA-MPS3: 3
0
Per PRA-MPS3: 1
0
Per PRA-ES8P2S: 2