9.4

Interconnection with B9512G or B8512G panel

Scenario: B9512G or B8512G + PRA + 1 Strobe
1
NAC
2
A
1
Clear strobe
2
NAC rack for strobes (R1002ULADA)
3
Notification appliance module (D192G)
4
8‑input Expansion Module (B208)
5
Control panel (B9512G or B8512G)
6
8‑input Expansion Module (B208)
7
Octo‑output module (B308)
8
PRAESENSA system
See i.e. PRAESENSA product overview, page 14
Bosch Security Systems B.V.
B
D
B8512G
D192G
or
3
B9512G
C
E
D192G
3
B208
4
PRA-FRP3-US
B926M
(LOC/ACU)
10
11
Underwriters Laboratories Listing Document (ULLD)
B208
F
6
5
B308
7
B308
7
A
Output signals from NAC (AC local, battery and
trouble)
B
Notification output signal wiring for clear strobe
C
Also for clear strobe, but can be used for second
strobe zone.
D
Notification input- and output‑signal wiring for clear
strobe
E
Also for clear strobe, but can be used for second
strobe zone.
F
SDI2 class b wiring
G
Connect the following output contact triggers from
the PRAESENSA output contacts to the B208 panel:
Alarm Triggers and Trouble Signals from
PRAESENSA to B9512G or B8512G panel.
Transfer of Control Signals
See Control outputs, page 79 .
H
Connect the following output contact triggers from
the B308 panel to the PRAESENSA input contacts:
Alarm Triggers to start the MNS and Fire audio
messages in PRAESENSA.