PRAESENSA
9.6

Generic interfacing with fire panel

Scenario: PRAESENSA with FACP (fire only) #
Remark: Multiple FRP panels are allowed, provided they are mounted adjacent to either the
fire panel or a fire annunciator that has control (Silence / Reset) buttons.
1
Clear fire strobes
2
NAC rack for fire strobes
3
FACP input contact module (addressable)
4
FACP (Fire Alarm Control Panel)
5
Isolator (if required)
6
FACP input contact module (addressable)
7
FACP output contact module (addressable
relays)
8
PRAESENSA system.
See i.e. PRAESENSA product overview, page 14 .
10
Loudspeaker / zones
See i.e. Amplifier outputs, page 39 and Amplifier
outputs, page 51
11
Items 15 and 16 must be mounted side by side
Bosch Security Systems B.V.
A
Output signals from NAC (AC local, battery and
trouble)
B
Notification output wiring for fire strobe
C
Interconnection wiring
D
Class b SLC wiring
E
Class b SLC wiring
F
Class b SLC wiring
G
(Max. 8) Input contact wiring (e.g. Fire system, fire
trigger, trouble, battery, AC, etc.).
See Control outputs, page 79 .
H
(Max. 8) Output contact wiring (e.g. Fire alarm, CO
alarm, etc.).
See Control inputs, page 78 .
I
Ethernet PoE (Class N) wiring
See First responder panel | PRA-FRPx-US, PRA-FRPx-
USNY, page 108 .
Underwriters Laboratories Listing Document (ULLD)
System Configuration | en 157
2021.12.21 | V0.15b | F.01U.402.882