Bosch PRAESENSA Manual page 42

Public address and voice alarm system
Hide thumbs Also See for PRAESENSA:
Table of Contents

Advertisement

42
en | Installation wiring
Single Class A wiring (A to B)
Figure 3.5: Single Class A wiring
A third loudspeaker connection topology is the so-called Class‑A loop, where the loudspeakers
are connected in a loop, starting at output A and ending at output B, with the end of the loop
being supervised with an end‑of‑line device.
Follow the procedure below to connect the loudspeakers according to this scheme.
1.
2.
3.
Output fault detection
Output fault detection can be tested with the following means:
Refer to
2021.12.21 | V0.15b | F.01U.402.882
D
+
+
Connect all loudspeaker in parallel in a loop‑through fashion. Observe equal polarity for
all loudspeakers. Connect one side of the loudspeaker cable to output A, observing
polarity.
Connect the other side of the loudspeaker cable to output B. In this case maintaining the
correct polarity is especially important, as reversal on one end will short circuit the
amplifier channel, not immediately, but when output B is activated in case of interruption
of one conductor.
Connect an end-of-line device to the end-of-line connection terminals. These terminals are
connected in parallel to output B, internally in the amplifier, to include supervision of the
output B connection.
Ground short detection: Connect between one of the output conductors, of one of the
loudspeaker outputs and safety ground, a 50 kohm resistor.
Short circuit: Connect a ≤ 500 mohm resistor between the plus and minus of output A or
output B, of one of the loudspeaker outputs.
Open circuit: Unplug one of the loudspeaker output connectors.
Field wire cable requirements, page 19
Underwriters Laboratories Listing Document (ULLD)
(EOL-US)
PRAESENSA
Bosch Security Systems B.V.