Troubleshooting - Dimplex EDL170-520RF Installation And User Instructions Manual

Air source heat pump water heater
Hide thumbs Also See for EDL170-520RF:
Table of Contents

Advertisement

8.6

Troubleshooting

Issue
The Heat Pump is not
working
No Hot Water
Condensates are not drain-
ing
Electrical backup is not
working
Do not adjust the settings on the thermostat.
Reset button (84
Check
- That the desired water temperature is higher than
the temperature of the water in the tank.
- There is power supply to the appliance.
- The green light is on.
- That the appliance is not in holiday mode (see Sec-
tion 7.7)
- That the air intake or ambient temperature is under
- That the timer has not been programmed to stop the
appliance operating ('Economy' light will be on (see
Section 7.3).
- If an error message is displayed on the screen
(see Section 8.8).
- That the volume consumed is not higher than the
- The time period the appliance operates is not too
- The water temperature is not set too low.
- The draining system for dirt or blockages:
Remove the cover (see Figure 18) and check the
opening.
- That tubes do not have bends or "U" shapes that can
collect water.
- That the end of the tube is not blocked off and has
access to open air.
- That your electricity provider or your timer is not
preventing the appliance from functioning, 'Economy'
symbol should be on (see Section 7.7).
- A heat-limiting safety thermostat for electrical
backup has not been activated after over-heating
(>84°C). If this is the case, reset it.
- Before resetting, check:
• that the heating element does not have limescale.
• clean or replace if necessary.
Table 5: Troubleshooting
o
C) on thermostat
Troubleshooting
- 7 o C or over +35 o C.
volume in the tank.
short (12hrs minimum if connected to piping).