Dip Switches - Trane TAM7A0A24H21SC Installer's Manual

Table of Contents

Advertisement

Dip Switches

Sca n to s e e a
vid e o o n s e ttin g
th e TAM7 DIP
S w itch e s .
Click or Scan to see a video on setting the
TAM7 DIP Switches
D D i i p p S S w w i i t t c c h h S S 1 1
Set the S1–1 and S1–2 dip switches for the OD
multiplier (tonnage) per the chart.
INDOOR MODEL
S1–1
OFF
OFF
TAM7A0A24H21SC
ON
ON
OFF
OFF
TAM7A0B30H21SC
ON
ON
OFF
OFF
TAM7A0C36H31SC
ON
ON
OFF
OFF
TAM7A0C42H31SC
ON
ON
OFF
OFF
TAM7A0C48H41SC
ON
ON
OFF
OFF
TAM7B0C60H51SB
ON
ON
N N o o t t e e : : The OD multiplier in conjunction with the CFM/
TON can be used to adjust total airflow for your
application.
Example: 4.5T x 370 CFM/TON = 1665 CFM
** Not an actual OD size
Set the S1–3 dip switch for AC or HP .
OD TYPE
HP
AC
38
S1–2
OD MULTIPLIER
OFF
2
ON
1.5
OFF
2.5
ON
3
OFF
2
ON
1.5
OFF
2.5
ON
3
OFF
3
ON
2
OFF
2.5
ON
3.5
OFF
3.5
ON
2.5
OFF
3
ON
4
OFF
4
ON
3
OFF
3.5
ON
4.5**
OFF
4.5**
ON
3.5
OFF
4
ON
5
S1–3
OFF
ON
OUTDOOR
OUTDOOR
HP
1
1
R4
S1
R NET 1
R NET 2
U1
Co o l Off De la y
R13
R14
Airflo w Co n tro l (AFC)
Set the S1–4 dip switch for the number of stages on
the outdoor unit.
OD STAGES
1
2
N N o o t t e e : : Refer to the field wiring diagram of the Outdoor
Unit to determine if the unit is 1 or 2 stage.
N N o o t t e e : : This dip switch should be changed while the
power is off or no demand is present. The power
must be shut off and then re-applied in order for
the AFC to recognize the change.
Set the S1–5 dip switch for the number of
compressors.
# COMPRESSORS
1
2
S 1
on
}
Ca p a c ity (To n s )
AC (S ys te m)
2 (S ta g e s )
2 (Co mp re s s o r)
INDOOR
on
CFM/To n
To rq u e
CFM
D9
S2
C10
+12V
S1–4
OFF
ON
S1–5
OFF
ON
18-GJ06D2-2A