Water Temp. And Flows - York YCAV0569 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

TECHNICAL DATA
MODEL
LEAVING WATER
NUMBER
TEMPERATURE (C°)
YCAV
MIN.
0569
4.4
0639
4.4
0679
4.4
0719
4.4
0739
4.4
0819
4.4
0889
4.4
0969
4.4
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 15.6°C, contact the nearest YORK office for application guidelines.
42
WATER TEMPERATURE AND FLOWS
TEMPERATURE AND FLOWS
(SI UNITS)
1
2
MAX.
15.6
15.6
15.6
15.6
15.6
15.6
15.6
15.6
COOLER FLOW
(l/s)
MIN.
MAX.
8.8
42.6
10.1
47.3
10.1
47.3
10.1
47.3
10.1
47.3
11.4
47.3
11.4
47.3
11.4
50.5
FORM 201.21-NM2 (616)
AIR ON
CONDENSOR (C°)
MIN.
MAX.
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
JOHNSON CONTROLS