Relay Output Boards; Vsd (Variable Speed Drive); Ac To Dc Rectifier - York YCAV0569 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

CHILLER ELECTRONIC COMPONENTS (CON'T)
Two 8 channel, 8 bit Digital to Analog Converters (D/A
Converter) on the Chiller Control Board supply the Feed
and Drain Valve Controller signals to allow the controller
to position the Flash Tank Feed and Drain Valves. The
Feed Valve controls the refrigerant level in the flash tank
while the Drain Valves controls superheat. The control
voltage to the Feed and Drain Valve Controller has a
range of 0-10.28 VDC.

RELAY OUTPUT BOARDS

Two or three Relay Output Boards are required to
operate the chiller. These boards convert 0-12VDC
logic levels outputs from the Chiller Control Board
to 115VAC levels used by contactors, relays, solenoid
valves, etc., to control system and chiller operation. The
common side of all relays on the Relay Output Board is
connected to +12VDC.
The open collector outputs of the Chiller Control Board
energize the DC relays on the Relay Output Board
by pulling one side of the relay coil to ground. When
not energized, both sides of the relay coils will be at
+12VDC potential.

VSD (Variable Speed Drive)

The VSD is a liquid cooled, transistorized, PWM
inverter packaged within the Control/Power cabinet.
The inverter is composed of four major sections: the AC
to DC rectifier section with precharge circuit, a DC link
filter section, a three phase DC to AC inverter section,
and an output RC suppression network.
JOHNSON CONTROLS

AC TO DC RECTIFIER

The AC to DC Rectifier circuit utilizes a semi-converter
made of three SCR/diode modules in a three phase
bridge configuration. Each SCR/Diode module contains
1 SCR and 1 diode. The modules are mounted on a
liquid cooled heatsink. This circuit rectifies the
incoming AC voltage to unfiltered DC, which is filtered
by the DC Link Filter.
A semi-converter (combination SCR/Diode)
configuration allows utilizing a separate pre-charge
circuit to limit the current in the DC link filter capacitors
when the VSD is first switched on. This is accomplished
by slowly turning on the SCR's to initially charge the
DC Bus. Once charged, the SCR's remain fully gated
LD10607
on during normal operation. This configuration also
provides a fast disconnect from main power when the
drive is switched off.
When the drive is called to run (leaving chilled liquid
temperature is > than the Setpoint + CR), the SCR/Diode
modules are turned on by the SCR trigger Board, allow-
ing the DC link filter capacitors to slowly precharge for
a period of 20 seconds.
The AC incoming line voltage is rectified by the full
three phase semi-converter bridge, made up of three
SCR/Diode modules, which provides pulsating DC to
the DC link Filter in the VSD.
FORM 201.21-NM2 (616)
6
LD10608
129

Advertisement

Table of Contents
loading