Water Temp. And Flows - York YCAV0157-0267 Installation Operation & Maintenance

60 hz air-cooled screw liquid chillers (150-260 tons). e/v high efficiency and s/p standard efficiency
Table of Contents

Advertisement

TECHNICAL DATA
MODEL
LEAVING WATER
NUMBER
TEMPERATURE (F°)
YCAV
MIN.
0157
40
0177
40
0187
40
0197
40
0207
40
0227
40
0247
40
0267
40
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest YORK office for application guidelines.
MODEL
LEAVING WATER
NUMBER
TEMPERATURE (C°)
YCAV
MIN.
0157
4.4
0177
4.4
0187
4.4
0197
4.4
0207
4.4
0227
4.4
0247
4.4
0267
4.4
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest YORK office for application guidelines.
42
WATER TEMPERATURE AND FLOWS
TEMPERATURE AND FLOWS
(ENGLISH UNITS)
1
2
MAX.
60
60
60
60
60
60
60
60
TEMPERATURE AND FLOWS
(SI UNITS)
1
2
MAX.
15.6
15.6
15.6
15.6
15.6
15.6
15.6
15.6
COOLER FLOW
(GPM)
MIN.
MAX.
140
675
160
750
160
750
160
750
160
750
160
750
180
750
180
800
COOLER FLOW
(l/s)
MIN.
MAX.
8.8
42.6
10.1
47.3
10.1
47.3
10.1
47.3
10.1
47.3
11.4
47.3
11.4
47.3
11.4
50.5
FORM 201.21-NM1 (616)
AIR ON
CONDENSOR (F°)
MIN.
MAX.
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
AIR ON
CONDENSOR (C°)
MIN.
MAX.
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
JOHNSON CONTROLS