Panel Checks; (Power On-Both System Switches Off) - York YCAV0569 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

TECHNICAL DATA
EQUIPMENT START-UP CHECK SHEET (CON'T)
chiller operation. Whenever the pump contacts are
used, the coil of the pump starter should be suppressed
with an RC suppressor (031-00808-000).

PANEL CHECKS

(POWER ON – BOTH SYSTEM SWITCHES "OFF")
You are about to turn power on to this
machine. Safety is Number One! Only
qualified individuals are permitted to
service this product. The qualified
individual furthermore is to be knowl-
edgeable of, and adhere to, all safe
work practices as required by NEC,
OSHA, and NFPA 70E. Proper per-
sonal protection is to be utilized where
and when required.
1. Assure the chiller OFF/ON UNIT switch at the bot-
tom of the keypad is OFF.
2. Apply 3-phase power to the chiller.
the optional panel circuit breaker if supplied. The
customer's disconnection devices can now be set to
ON.
3. Verify the control panel display is illuminated.
4. To prevent the compressors from starting, assure
that the system switches under the SYSTEM
SWITCHES key are in the OFF position.
5. Verify that the voltage supply corresponds to the
unit requirement and is within the limits given in
the Technical Data Section.
6. Ensure the heaters on each compressor are on using
a clamp-on ammeter. Heater current draw is approx.
3A.
7 . Verify the "Factory Set" Overload Potentiometers
on the VSD Logic Board are set correctly (correct
settings are provided on Page 268). Press the VSD
DATA key and using the arrow keys, scroll to the
compressor overload settings. Verify the "Factory
Set" overload potentiometer(s) on the VSD logic
board (see FIG. 16) are set correctly. In the un-
likely event that they are not set correctly, adjust
the potentiometers until the desired values are
achieved.
122
Adjust the potentiometers, if needed, using the table on
Page 267. The locations of the potentiometers are shown
in FIG. 16, Page 108. The potentiometers are Sys 1=R19,
Sys 2=R64, Sys 3=R42, and Sys 4=R86.
Record the Overload Potentiometer settings below:
Compressor Overload Setting:
System 1 = ______________ Amps
Turn ON
System 2 = ______________ Amps
System 3 = ______________ Amps
System 4 = ______________ Amps
8. Press the STATUS Key. If the following message
appears, immediately contact YORK Product
Technical Support. The appearance of this message
may mean the chiller has lost important factory
programmed information. The serial num-
ber and other important data may need to be
reprogrammed.
UNIT WARNING: INVALID SERIAL NUMBER
ENTER UNIT SERIAL NUMBER
FORM 201.21-NM2 (616)
The VSD is powered up and live. High
voltage exists in the area of the cir-
cuit board on the bus bars, VSD Pole
Assemblies, and wiring to the input
inductor.
Incorrect settings of the potentiometers
may cause damage to the equipment.
Changing the programming of this
feature requires the date and time to
be set on the chiller prior to program-
ming. Additional information regard-
ing this message and how to enter the
serial number with the factory provided
password is outlined in the SERIAL
NUMBER PROGRAMMING informa-
tion on Page 235.
JOHNSON CONTROLS

Advertisement

Table of Contents
loading

Table of Contents