Commissioning

5.1 Commissioning with SENTRON powerconfig app

5.1
Commissioning with SENTRON powerconfig app
The metering and communication-capable SENTRON circuit protection devices are put into
operation with the SENTRON powerconfig commissioning app for mobile devices, also known
as powerconfig mobile.
Note
An exact description on how to use the app can be found in the Installation Manual
(https://support.industry.siemens.com/cs/ww/en/view/109791805).
First the 7KN Powercenter 1000 data transceiver must be added. This can happen in the
following ways:
• WLAN searches if the 7KN Powercenter 1000 and the mobile device are located in the
same network.
• Bluetooth searches of all available devices. To do so, the Bluetooth mode must be
activated with a short button press and the Bluetooth PIN code must be entered after
scanning the Data Matrix Code. The PIN code can also be entered manually with the code
printed on the side of the device.
• Manual entry of the IP address of the 7KN Powercenter 1000. This may be necessary if at
first all devices are to be added offline or in case of a VPN connection the IP address must
be entered manually for security reasons. In order for the data transceiver to set up a
communication with the smartphone or tablet, it must be connected to the
24 V DC-power supply. After the supply voltage has been applied and the IP address has
been determined, it can be subsequently changed in the app.
Then the individual communication-capable terminal devices must be added. To do so, the
DMC must be scanned with the "RF code" marking of the individual devices, this contains the
device type, MAC address and the installation code. Alternatively the scanning step can be
skipped and the aforementioned information can be entered manually. These are printed on
the side of the device.
A clear name or plant identifier must be provided when adding the communication-capable
terminal devices so that the devices can be distinguished from one another.
Note
Scanning can also be performed without powering the devices. This is necessary if the RF
codes are not accessible when fully installed (e.g. possible with the 3NA COM fuse) or the
devices are not allowed to be switched off to scan the RF code. The RF code of the 5SL6 COM
miniature circuit breakers and 5SV6 COM arc fault detection devices can only be scanned if
the operating lever is set to the Off position.
Two Data Matrix Codes need to be scanned for the 3NA COM fuse. First the one of the
electronic module and then the one of the fuse link
The 3NA COM fuse link and the electronic module can still be scanned when installed, e.g. in
a 3NP fuse switch disconnector, if necessary, the flashlight function of the mobile device
must be used to illuminate the code.
40
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01