Messages; Measured Values And Upper Limit Violation - Siemens Sentron 7KN POWERCENTER 1000 Manual

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

Functions

6.2 Messages

6.2
Messages
6.2.1

Measured values and upper limit violation

The following messages are possible due to upper limit violations:
Description
End of maximum set operating periods
End of maximum set operating duration with
definable load
End of maximum set switching cycles
End of maximum set short-circuit disconnec-
tions
End of maximum set tripping operations
Reaching set temperature
Overcurrent alarm 1 in % of rated current
Overcurrent alarm 2 in % of rated current
Undercurrent alarm 1 in % of rated current
Undercurrent alarm 2 in % of rated current
Overvoltage alarm 1 in volts
Overvoltage alarm 2 in volts
Undervoltage alarm 1 in volts
Undervoltage alarm 2 in volts
Voltage underflow AFDD trip
Base line is an average temperature that is determined over an adjustable time.
1)
Base line is an average current that is determined over an adjustable time.
2)
Base line is the average voltage which is fixed according to the standard, constant at 195 V and a hysteresis of 10%.
3)
Note
Not all alarms are activated by default. All alarms can each be switched on or off.
The respective alarms can be activated or even deactivated. A message is not displayed if they
are deactivated and the device LEDs do not flash according to the pattern described above
(see Chapter LED signaling (Page 37)). Furthermore, there are adjustable setpoint values that
generate messages when they are exceeded. In addition, a hysteresis value can be set for the
alarms for current, voltage and temperature. An alarm is activated if a threshold value is
exceeded. If the measured value falls short of the setpoint value including the set hysteresis,
the alarm status is left again.
Chapter Measurement settings (Page 71) described which parameters are available with the
respective units, value ranges and default settings.
The aforementioned warnings are displayed in the device overviews for the respective
measured values. Furthermore, these are displayed in the Messages view with a time stamp.
56
Possible message sources:
Default POC 1000 5ST3 COM 5SL6 COM
Inactive
Inactive
Inactive
Active
Inactive
Active
1)
Active
2)
Inactive
2)
Inactive
2)
Inactive
2)
Inactive
Inactive
Inactive
Inactive
Active
3)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01