5Sl6 Com Miniature Circuit Breaker - Siemens Sentron 7KN POWERCENTER 1000 Manual

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

10.3

5SL6 COM miniature circuit breaker

Designation
Order number
Product name
Tripping characteristic class
Operational current for AC rated value
Supply voltage for AC rated value
Breaking capacity current acc. to EN 60898 rated value
Available measurement data
Energy limiting class
Minimum connectable conductor cross-section, solid
Maximum connectable conductor cross-section, solid
Minimum connectable conductor cross-section, stranded
Maximum connectable conductor cross-section, stranded
Minimum connectable conductor cross-section, finely
stranded with end sleeve
Maximum connectable conductor cross-section, finely
stranded with end sleeve
Minimum tightening torque
Maximum tightening torque
Product expansion can be installed
Number of poles
Product function with switching neutral conductor
IP degree of protection
Pollution degree
Overvoltage category
Number of modular width units
Minimum ambient temperature during storage
Maximum ambient temperature during storage
Maximum ambient temperature during operation
Minimum ambient temperature during operation
Ambient temperature with 95% relative air humidity
Number of test cycles for environmental testing in accord-
ance with IEC 60068-2-30
Insulation voltage for AC rated value
Impulse withstand voltage, rated value
Minimum operating voltage
Maximum operating voltage with single-phase operation
with AC
Insulation voltage with single-phase operation with AC rated
value
Mounting type
Reference ID in accordance with IEC 81346-2:2009
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
10.3 5SL6 COM miniature circuit breaker
Value
5SL60xx-yMC (xx = 02, 04, 06, 08, 10, 13, 16, 20, 25, 32; y
= 6 or 7)
5SL6 COM compact miniature circuit breaker
B and C
2 A, 4 A, 6 A, 8 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A
230 V
6 kA
voltage, current, active power, apparent power, reactive
power, active energy, line frequency, power factor, tempera-
ture, switching cycles, operating hours, tripping operation,
warnings
3
0.75 mm
2
16 mm
2
0.75 mm
2
16 mm
2
0.75 mm
2
10 mm
2
1.2 Nm
2 Nm
Yes
1P+N
Yes
IP20, with connected conductors
2
III
1
-40°C
75°C
60°C
-25°C
60°C
28
250 V
4000 V
195 V
253 V
250 V
DIN rail
F
Technical specifications
89

Hide quick links:

Advertisement

Table of Contents
loading