Samsung MXJ-YA1509 Series Installation Manual page 26

Table of Contents

Advertisement

   
2. 2.
 Preparation
 Preparation     for installation
Item
Item
   
- Louver specification is
- Louver specification is
Louver
Louver
- Can you clear 500mm(20inch)
- Can you clear 500mm(20inch)
 Top
 Top
discharge
discharge
unit
unit
- Can you access the outdoor
- Can you access the outdoor
-Is the service space available?
-Is the service space available?
Side
Side
discharge
discharge
unit
unit
- Can you have more than
- Can you have more than
- Is the outdoor unit located
- Is the outdoor unit located
- Is the installation location
- Is the installation location
Corrosion
Corrosion
in the
in the
outdoor
outdoor
unit
unit
- All units are concentrated in a
- All units are concentrated in a
Outdoor
Outdoor
- All units are concentrated in a
- All units are concentrated in a
unit
unit
installation
installation
for installation
Pre-check checkpoint
Pre-check checkpoint
suggested ?
suggested ?
or more from the front of the
or more from the front of the
outdoor unit and
outdoor unit and
300mm(12inch) or more from
300mm(12inch) or more from
the rear?
the rear?
[Tray and interfering pipes
[Tray and interfering pipes
included.]
included.]
unit?
unit?
1500mm(60inch) in front of
1500mm(60inch) in front of
the outdoor unit?
the outdoor unit?
close to a bathroom/ kitchen
close to a bathroom/ kitchen
vent/cooling tower or air vent?
vent/cooling tower or air vent?
close to a beach or hot
close to a beach or hot
spring?
spring?
specific area on a rooftop or
specific area on a rooftop or
in a gallery?
in a gallery?
specific area on a rooftop or
specific area on a rooftop or
in a gallery?
in a gallery?
Handling methods and
Handling methods and
   
guideline
guideline
- Louver angle should be less than
- Louver angle should be less than
20°
20°
- Opening rate of more than 80%.
- Opening rate of more than 80%.
- Select a louver with a smooth
- Select a louver with a smooth
cross section.
cross section.
(Do not use a rainwater
(Do not use a rainwater
prevention louver.)
prevention louver.)
 2 level stacking not allowed.
 2 level stacking not allowed.
- Possible when the metal frame is
- Possible when the metal frame is
used. Height of 300mm(12inch),
used. Height of 300mm(12inch),
side of 100mm(4inch)
side of 100mm(4inch)
 When the front and the rear are
 When the front and the rear are
face to face, secure the minimum
face to face, secure the minimum
distance of 3000mm between
distance of 3000mm between
outdoor units.
outdoor units.
 Corrosion in the outdoor unit and
 Corrosion in the outdoor unit and
the pipe may possibly cause
the pipe may possibly cause
refrigerant leakage
refrigerant leakage
- Select other location where it is
- Select other location where it is
free from salty wind and
free from salty wind and
intoxicating gas
intoxicating gas
 Check the CFD simulation.
 Check the CFD simulation.
- Request to HQ's.
- Request to HQ's.
26
26
Picture
Picture
   
 To secure service area
 To secure service area
2-level stacking prohibited.
2-level stacking prohibited.
Installation near toxic gas
Installation near toxic gas
source is prohibited.
source is prohibited.
Where units stand close to
Where units stand close to
each other, it possibly lacks
each other, it possibly lacks
sufficient air circulation
sufficient air circulation
   