Carrier WSHP Open v3 Integration Manual page 12

Hide thumbs Also See for WSHP Open v3:
Table of Contents

Advertisement

Communications wiring
Baud DIP switch settings
Baud rate
9,600 bps
19.2 kbps
38.4 kbps
76.8 kbps
Set the remaining DIP switches as follows:
4
BACnet MS/TP DIP switch settings
8
Off
The following example shows the DIP switches set for 76.8k (Carrier default), and BACnet MS/TP.
Connect the BACnet MS/TP network to the controller's J19 Network Comm port. Connect to Net+, Net-, and
5
SHLD.
Wire specifications
A dedicated 22 AWG shielded twisted pair wire (EIA 485)
Maximum wire length 2000 feet (610 meters) or 32 nodes
Devices should be daisy-chained and not star-wired
Attach the drain/shield wire to both ends of the network segment and through every controller
NOTE Use the same polarity throughout the network segment.
Turn on the WSHP Open's power.
6
WSHP Open v3
Integration Guide
2
Off
On
Off
On
7
6
5
Off
Off
Off
8
1
Off
Off
On
On
4
3
On
Off
CARRIER CORPORATION ©2021
All rights reserved