To set up the WSHP Open for the LonWorks Option Card (Part #LON-OC)
Turn off the WSHP Open's power.
1
NOTES
Changes made to the switches when the controller is on will not take effect until the power has been
○
cycled!
The controller's rotary address switches are not used when the LON-OC is installed. That's because each
○
LON-OC has a 48-bit Neuron ID that makes it unique on the LonWorks network.
Set the SW3 DIP switches for LonWorks as follows:
2
8
Off
Plug the LonWorks Option Card's ribbon cable into Comm Option port J15 on the controller. See illustration
3
below.
CAUTION! The controller must be OFF before being connected.
WSHP Open v3
Integration Guide
7
6
5
On
On
Off
19
4
3
On
Off
CARRIER CORPORATION ©2021
Communications wiring
2
1
Off
On
All rights reserved