Carrier WSHP Open v3 Integration Manual page 45

Hide thumbs Also See for WSHP Open v3:
Table of Contents

Advertisement

Point
Point Name
Access
Minimum Cooling SAT R/W
Setpoint Adjustment
R/W
Range
BAS On / Off
R/W
ZS Sensor
R
Configuration
Space Relative
R
Humidity
Space Temp Source
R
Fan Off Delay
R/W
Air Source Supply Air
R
Temp
Water Loop Temp
R
Aux Heat Boiler Water
R
Temp
Airside Linkage
R
Source Water Linkage R
System Heating
R
Demand Level
Airside Linkage
R
Occ Override Delay
R/W
Loop Pump Request
R
Source Water Linkage R
Aux Heat HW Pump
R
Status
System Cooling
R
Demand Level
Filter Runtime
R
Compressor Capacity
R
Air Source Mode
R
WSHP Open v3
Integration Guide
Default
Units
Value
°F
50
°F
5
(1) Inactive
1
(2) Occupied
(3) Unoccupied
(0) Normal
(1) Alarm
%rh
(1) Sensor Failure
(2) SPT Sensor
(3) T55 / T56
(4) Network
(5) Airside
Linkage
(6) Locked Value
seconds
90
°F
°F
°F
(0) Normal
(1) Alarm
(0) Normal
(1) Alarm
no units
(0) Not Active
(1) Active
min
15
no units
(0) Not Active
(1) Active
(0) Off
(1) On
no units
hr
%
(1) Off
(2) Warmup
(3) Heat
(4) Cooling
(5) Freecool
(6) Pressure
(7) Evac
(8) Vent
Appendix A: Network Points List for WSHP Open
BACnet
BACnet Point Name
sat_cl_min
stpt_adj_range
keypad_ovrde
zs_config_fail
space_rh
spt_status
fan_delay_off
link_sat
link_cwt
link_hwt
air_linkage_fail
cond_water_linkage_fail
heat_demand_level
a_link_status
occ_ovr_delay
loop_request
cw_link_status
hw_pump
cool_demand_level
filter_rntm
comp_cap
link_ahu_mode
41
Modbus
BACnet
Modbus
Modbus
Object ID
Register
Register #
Type
AV:83003
Input
61
Register
(Float)
AV:9015
Holding
101
Register
(Float)
MSV:1001
Holding
133
Register
(Signed)
BV:7055
Discrete
63
Input
AV:1011
Input
103
Register
(Float)
MSV:2003
AV:9024
AV:2608
AV:2701
AV:2702
BV:7030
BV:7031
AV:9036
BV:2601
AV:9028
AV:2024
BV:2701
BV:2703
AV:9006
AV:2015
AV:5001
Input
165
Register
(Float)
MSV:2005
-
-
CARRIER CORPORATION ©2021
All rights reserved