Appendix A: Network Points List for WSHP Open
Point
Point Name
Access
System Mode
R
Occ Relative Humidity
R/W
Setpoint
Optimal Start
R/W
Smoke Detector
R
Contact
Effective Cool
R
Setpoint
Setpoint
R/W
Heating Lockout
R/W
Temperature
Power Fail Restart
R/W
Delay
Setpoint
R/W
Filter Service Alarm
R/W
Timer
Indoor Air Quality CO2
R
(ppm)
Setpoint
R/W
System Outdoor Air
R/W
Temperature
System Setpoint
R/W
Adjustment
Reset Filter Alarm
R/W
Effective Heat
R
Setpoint
Maximum Heating
R/W
SAT
WSHP Open v3
Integration Guide
Default
Units
Value
(1) Off
(2) Fan Only
(3) Economize
(4) Cooling
(5) Heating
(6) Cont Fan
(7) Test
(8) Start Delay
%rh
60
hr
1
(0) Alarm / Open
(1) Normal /
Closed
°F
°F
°F
65
seconds
180
°F
hr
600
ppm
°F
°F
-999
°F
-999
(0) Off
(0) Off
(1) On
°F
°F
110
BACnet
BACnet Point Name
run_status
occ_dehum_stpt
optm_start
smk_detect
eff_cl_stpt
unocc_cl_stpt
oat_ht_lockout
start_delay
occ_cl_stpt
filter_service_hrs
iaq
unocc_ht_stpt
system_oat
system_stpt_adj
filter_rntm_clr
eff_ht_stpt
sat_ht_max
40
Modbus
BACnet
Modbus
Modbus
Object ID
Register
Register #
Type
MSV:2002
Input
1
Register
(Signed)
AV:3011
Holding
83
Register
(Float)
Holding
AV:9026
147
Register
(Float)
BV:1004
Discrete
1
Input
AV:3005
Input
55
Register
(Float)
AV:3003
Holding
15
Register
(Float)
AV:9003
Holding
69
Register
(Float)
AV:9007
Holding
127
Register
(Float)
AV:3001
Holding
9
Register
(Float)
AV:2019
Holding
67
Register
(Float)
AV:1009
Input
73
Register
(Float)
AV:3004
Holding
17
Register
(Float)
AV:1901
Holding
119
Register
(Float)
AV:1913
Holding
53
Register
(Float)
BV:7517
Coil
22
AV:3006
Input
57
Register
(Float)
AV:83004
Input
41
Register
(Float)