Appendix A: Network Points List for WSHP Open
Point
Point Name
Access
Occ Relative Humidity
R/W
Setpoint
Optimal Start
R/W
Smoke Detector
R
Contact
Effective Cool
R
Setpoint
Setpoint
R/W
Heating Lockout
R/W
Temperature
Power Fail Restart
R/W
Delay
Setpoint
R/W
Filter Service Alarm
R/W
Timer
Indoor Air Quality
R
CO2 (ppm)
Setpoint
R/W
System Outdoor Air
R/W
Temperature
System Setpoint
R/W
Adjustment
Reset Filter Alarm
R/W
Effective Heat
R
Setpoint
Maximum Heating
R/W
SAT
Minimum Cooling SAT R/W
Setpoint Adjustment
R/W
Range
BAS On / Off
R/W
ZS Sensor
R
Configuration
Space Relative
R
Humidity
Compressor Capacity
R
SPT Sensor
R
WSHP Open v3
Integration Guide
Default
Units
Value
%rh
60
hr
1
(0) Alarm / Open
(1) Normal /
Closed
°F
°F
°F
65
seconds
180
°F
hr
600
ppm
°F
°F
-999
°F
-999
(0) Off
(0) Off
(1) On
°F
°F
110
°F
50
°F
5
(1) Inactive
1
(2) Occupied
(3) Unoccupied
(0) Normal
(1) Alarm
%rh
%
(0) Normal
(1) Alarm
N2
LonWorks
N2
N2
SNVT Type
Network
Network
Point Type
Point
Address
ADF
36
nviOcRHSP
ADF
61
nviOptmStart
BI
1
nvoSmkDetect
ADF
22
nvoEffCoolSP
ADF
7
nviUnoccClSP
ADF
29
nviHtLckTmp
ADF
58
nviUntStrDly
ADF
4
nviOccCoolSP
ADF
28
nviFltAlmTm
ADF
31
nvoIAQ
ADF
8
nviUnoccHtSP
ADF
54
nviSysOAT
ADF
68
nviSysSptAdj
BO
22
nviRstFilAlm
ADF
23
nvoEffHeatSP
ADF
33
nviMaxHtSAT
ADF
42
nviMinClSAT
ADF
45
nviSPAdjRng
ADI
1
nviBASOnOff
BI
63
nvoZsCfgFail
ADF
46
nvoSpaceRH
ADF
72
BI
38
44
SNVT Name
SNVT_lev_percent(81)
SNVT_time_hour(124)
SNVT_switch(95)
SNVT_temp_p(105)
SNVT_temp_p(105)
SNVT_temp_p(105)
SNVT_time_sec(107)
SNVT_temp_p(105)
SNVT_time_hour(124)
SNVT_ppm(29)
SNVT_temp_p(105)
SNVT_temp_p(105)
SNVT_temp_p(105)
SNVT_switch(95)
SNVT_temp_p(105)
SNVT_temp_p(105)
SNVT_temp_p(105)
SNVT_temp_p(105)
SNVT_count_inc(9)
SNVT_switch(95)
SNVT_lev_percent(81)