▪ Preparing the installation site
▪ Preparing the water piping
▪ Preparing the electrical wiring
6.2

Preparing installation site

Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit must be covered.
Choose the installation location with sufficient place for carrying the
unit in and out of the site.
6.2.1
Installation site requirements of the
outdoor unit
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
Mind the following spacing guidelines:
>250/400
>350
b
a
>250
(mm)
a
Air outlet
b
Air inlet
INFORMATION
If shut-off valves are installed on the unit, provide a
minimum space of 400 mm at the air inlet side. If shut‑off
valves are NOT installed on the unit, provide a minimum
space of 250 mm.
NOTICE
▪ Do NOT stack the units on each other.
▪ Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet
causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
EWAQ+EWYQ004+005BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P492900-1 – 2017.06
b
>250/400
a
(mm)
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
Note: If the sound is measured under actual installation
conditions, the measured value might be higher than the sound
pressure level mentioned in Sound spectrum in the data book due
to environmental noise and sound reflections.
INFORMATION
The sound pressure level is less than 70 dBA.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
It is NOT recommended to install the unit in the following places
because it may shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present
Seaside installation. Make sure the outdoor unit is NOT directly
exposed to sea winds. This is to prevent corrosion caused by high
levels of salt in the air, which might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
a
6 Preparation
b
a
b
c
Installer reference guide
21