Setting Up The Power Consumption Control; Permanent Power Limitation; Power Limitation Activated By Digital Inputs - Daikin EWAQ004BAVP Installer's Reference Manual

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ004BAVP:
Table of Contents

Advertisement

Power meter types
▪ Power meter 1: Single-phase power meter.
▪ Power meter 2:
▪ In case of a single-phase backup heater configuration, use a
single-phase power meter.
▪ In other cases, use a three-phase power meter.
Example
Three-phase backup heater:
0
0
0
58 0
0
58 0
1 5 0
1 5 0
a
b
c
d
  
 
e
e
f
g
h
i
j
A
B
C
D
A
Outdoor unit
B
Control box
C
Option box
D
Backup heater kit
a
Electrical cabinet (L
supply
b
Electrical cabinet (L
supply
c
Power meter (L
/N)
1
d
Power meter (L
/L
1
e
Fuse (L
/N)
1
f
Fuse (L
/L
/L
/N)
1
2
3
g
Outdoor unit (L
/N)
1
h
Control box (L
/N)
1
i
Option box (L
/N)
1
j
Backup heater (L
1
5.5
Setting up the power consumption
control
▪ The power consumption control:
▪ Allows you to limit the power consumption of the entire system
(sum of the outdoor unit, control box EKCB07CAV3, option box
EK2CB07CAV3, and the backup heater kit).
▪ Configuration: Set the power limitation level and how it has to
be achieved via the user interface.
▪ The power limitation level can be expressed as:
▪ Maximum running current (in A)
▪ Maximum power input (in kW)
▪ The power limitation level can be activated:
▪ Permanently
▪ By digital inputs
5.5.1

Permanent power limitation

Permanent power limitation is useful to assure a maximum power or
current input of the system. In some countries, legislation limits the
maximum power consumption for space heating.
EWAQ+EWYQ004+005BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P492900-1 – 2017.06
/N): Preferential kWh rate power
1
/L
/L
/N): Normal kWh rate power
1
2
3
/L
/N)
2
3
/L
/L
/N)
2
3
5 Application guidelines
P
i
a
DI
b
t
P
Power input
i
t
Time
DI
Digital input (power limitation level)
a
Power limitation active
b
Actual power input
Setup and configuration
▪ No additional equipment needed.
▪ Set the power consumption control settings in [A.6.3.1] via the
user
interface
(for
the
"8 Configuration" on
page 46):
▪ Select full time limitation mode
▪ Select the type of limitation (power in kW or current in A)
▪ Set the desired power limitation level
NOTICE
Mind the following guidelines when selecting the desired
power limitation level:
▪ Set a minimum power consumption of ±3.6  kW to
guarantee defrost operation. Otherwise, if defrosting is
interrupted several times, the heat exchanger will
freeze up.
▪ Set a minimum power consumption of ±3  kW to
guarantee space heating by allowing backup heater
step 1.
5.5.2
Power limitation activated by digital
inputs
Power limitation is also useful in combination with an energy
management system.
The power or current of the entire Daikin system is limited
dynamically by digital inputs (maximum four steps). Each power
limitation level is set via the user interface by limiting one of the
following:
▪ Current (in A)
▪ Power input (in kW)
The energy management system (field supply) decides the activation
of a certain power limitation level. Example: To limit the maximum
power of the entire house (lighting, domestic appliances, space
heating...).
A
B
C
X2M
A
Outdoor unit
B
Control box
C
Option box
D
Backup heater kit
F
Energy management system
a
Power limitation activation (4 digital inputs)
b
Backup heater
description
of
all
settings,
D
b
a
F
Installer reference guide
see
19

Advertisement