Daikin EWAQ004BAVP Installer's Reference Manual page 87

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ004BAVP:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
A.2.2.F.2
[C-09]
Alarm output
A.2.2.F.3
[D-08]
External kWh meter 1
A.2.2.F.4
[D-09]
External kWh meter 2
A.2.2.F.5
[C-08]
External sensor
A.2.2.F.6
[D-04]
PCC by digital inputs
└─ Capacities
A.2.3.2
[6-03]
BUH: step 1
A.2.3.3
[6-04]
BUH: step 2
└─ Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1
LWT setpoint mode
A.3.1.1.2.1
[9-01]
Temperature range
A.3.1.1.2.2
[9-00]
Temperature range
A.3.1.1.2.3
[9-03]
Temperature range
A.3.1.1.2.4
[9-02]
Temperature range
A.3.1.1.5
[8-05]
Modulated LWT
A.3.1.1.7
[9-0B]
Emitter type
└────────────────── Delta T source
A.3.1.3.1
[9-09]
Heating
A.3.1.3.2
[9-0A]
Cooling
└─ Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
A.3.2.1.2
[3-06]
Room temp. range
A.3.2.1.3
[3-09]
Room temp. range
A.3.2.1.4
[3-08]
Room temp. range
A.3.2.2
[2-0A]
Room temp. offset
A.3.2.3
[2-09]
Ext. room sensor offset
A.3.2.4
Room temp. step
└─ Operation range
A.3.3.1
[4-02]
Space heating OFF temp
A.3.3.2
[F-01]
Space cooling On temp
└─ Heat sources
└─ Backup heater
A.5.1.1
[4-00]
Operation mode
A.5.1.3
[4-07]
Enable BUH step 2
A.5.1.4
[5-01]
Equilibrium temp.
└─ System operation
└─ Auto restart
A.6.1
[3-00]
└─ Preferential kWh rate
A.6.2.1
[D-00]
Allowed heaters
A.6.2.2
[D-05]
Forced pump OFF
└─ Pwr consumpt. Control
A.6.3.1
[4-08]
Mode
A.6.3.2
[4-09]
Type
A.6.3.3
[5-05]
Amp. value
A.6.3.4
[5-09]
kW value
A.6.3.5.1
[5-05]
Amp. limits for DI
A.6.3.5.2
[5-06]
Amp. limits for DI
A.6.3.5.3
[5-07]
Amp. limits for DI
A.6.3.5.4
[5-08]
Amp. limits for DI
A.6.3.6.1
[5-09]
kW limits for DI
(*1) EWYQ*_(*2) EWAQ*
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (cooling)
Maximum temp (cooling)
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (cooling)
Maximum temp (cooling)
Limit DI1
Limit DI2
Limit DI3
Limit DI4
Limit DI1
Range, step
Default value
R/W
0: Normally open
1: Normally closed
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
0: No
1: Yes
R/W
0~10kW, step: 0,2kW
3kW
R/W
0~10kW, step: 0,2kW
0kW
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
R/W
15~37°C, step: 1°C
25°C
R/W
37~55°C, step: 1°C
55°C
R/W
5~18°C, step: 1°C
5°C
R/W
18~22°C, step: 1°C
22°C
R/W
0: No
1: Yes
R/W
0: Quick
1: Slow
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
12~18°C, step: A.3.2.4
16°C
R/W
18~30°C, step: A.3.2.4
30°C
R/W
15~25°C, step: A.3.2.4
15°C
R/W
25~35°C, step: A.3.2.4
35°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: 0,5 °C
1: 1 °C
R/W
14~35 °C, step: 1°C
25°C
R/W
10~35°C, step: 1°C
20°C
R/W
0~2
0: Disabled
1: Enabled
R/W
0: No
1: Yes
R/W
-15~35°C, step: 1°C
-4°C
R/W
0: No
1: Yes
R/W
0~3
0: None
2: BUH only
3: All heaters
R/W
0: Forced off
1: As normal
R/W
0: No limitation
1: Continuous
2: Digital inputs
R/W
0: Current
1: Power
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
3/7
Installer setting at variance with
default value
Date
Value
4P469115-1B - 2017.06