Daikin EWAQ004BAVP Installer's Reference Manual page 55

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ004BAVP:
Table of Contents

Advertisement

#
Code
[7.4.2.4]
[8-08]
Eco (cooling)
[9‑03]°C~[9‑02]°C (default: 20°C)
Preset leaving water temperature (shift value) for the main leaving
water temperature zone in case of weather dependent
[7.4.2.5]
N/A
Comfort (heating)
–10°C~+10°C (default: 0°C)
[7.4.2.6]
N/A
Eco (heating)
–10°C~+10°C (default: –2°C)
[7.4.2.7]
N/A
Comfort (cooling)
–10°C~+10°C (default: 0°C)
[7.4.2.8]
N/A
Eco (cooling)
–10°C~+10°C (default: 2°C)
Temperature ranges (leaving water temperatures)
The purpose of this setting is to prevent selecting a wrong (i.e. too
hot or too cold) leaving water temperature. Therefore the available
desired heating temperature range and desired cooling temperature
range can be configured.
NOTICE
In case of a floor heating application it is important to limit
the:
▪ maximum leaving water temperature at heating
operation according to the specifications of the floor
heating installation.
▪ the minimum leaving water temperature at cooling
operation to 18~20°C to prevent condensation on the
floor.
NOTICE
▪ When adjusting the leaving water temperature ranges,
all desired leaving water temperatures are also
adjusted to guarantee they are between the limits.
▪ Always balance between the desired leaving water
temperature with the desired room temperature and/or
the capacity (according to the design and selection of
the
heat
emitters).
temperature is the result of several settings (preset
values, shift values, weather dependent curves,
modulation). As a result, too high or too low leaving
water temperatures could occur which lead to
overtemperatures or capacity shortage. By limiting the
leaving water temperature range to adequate values
(depending on the heat emitter), such situations can be
avoided.
Example: Set the minimum leaving water temperature to 28°C to
avoid NOT to be able to heat up the room: leaving water
temperatures
MUST
be
sufficiently
temperatures (in heating).
#
Code
Leaving water temperature range for the main leaving water
temperature zone
[A.3.1.1.2.2] [9-00]
Maximum temp (heating)
37°C~55°C (default: 55°C)
EWAQ+EWYQ004+005BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P492900-1 – 2017.06
Description
The
desired
leaving
water
higher
than
the
room
Description
#
Code
[A.3.1.1.2.1] [9-01]
Minimum temp (heating)
15°C~37°C (default: 25°C)
[A.3.1.1.2.4] [9-02]
Maximum temp (cooling)
18°C~22°C (default: 22°C)
[A.3.1.1.2.3] [9-03]
Minimum temp (cooling)
5°C~18°C (default: 5°C)
Leaving water temperature overshoot temperature
This function defines how much the water temperature may rise
above the desired leaving water temperature before the compressor
stops. The compressor will startup again when the leaving water
temperature drops below the desired leaving water temperature.
This function is ONLY applicable in heating mode.
#
Code
N/A
[9-04]
1°C~4°C (default: 1°C)
Leaving water temperature compensation around 0°C
In heating operation, the desired leaving water temperature is locally
increased
around
an
outdoor
compensation can be selected when using an absolute or a weather
dependent desired temperature (see illustration below). Use this
setting to compensate for possible heat losses of the building due to
the evaporation of melted ice or snow (e.g. in cold region countries).
T
T
t
t
L
L
R
R
T
A
0°C
0°C
a
b
a
Absolute desired LWT
b
Weather dependent desired LWT
#
Code
N/A
[D-03]
▪ 0 (disabled)
▪ 1 (enabled) L=2°C,
R=4°C (−2°C<T
▪ 2 (enabled) L=4°C,
R=4°C (−2°C<T
▪ 3 (enabled) L=2°C,
R=8°C (−4°C<T
▪ 4 (enabled) L=4°C,
R=8°C (−4°C<T
Leaving water temperature maximum modulation
ONLY applicable in room thermostat control and when modulation is
enabled. The maximum modulation (=variance) on the desired
leaving water temperature decided on the difference between the
actual and desired room temperature, e.g. 3°C modulation means
the desired leaving water temperature can be increased or lowered
by 3°C. Increasing the modulation results in better performance (less
On/OFF, faster heat up), but note that depending on the heat
emitter, there MUST ALWAYS be a balance (refer to the design and
selection of the heat emitters) between the desired leaving water
temperature and the desired room temperature.
#
Code
N/A
[8-06]
0°C~10°C (default: 3°C)
Weather dependent cooling allowance
ONLY applicable for EWYQ004+005BAVP. It is possible to disable
weather dependent cooling, meaning the desired leaving water
temperature in cooling operation does NOT depend on the outdoor
ambient
temperature
and
this
dependent is selected or NOT.
8 Configuration
Description
Description
temperature
of
0°C.
T
A
Description
<2°C)
A
<2°C) (default)
A
<4°C)
A
<4°C)
A
Description
regardless
whether
weather
Installer reference guide
This
55

Advertisement

Table of Contents
loading

Table of Contents