Code
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1]
[5-09]
Limit DI1
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.2]
[5-0A]
Limit DI2
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.3]
[5-0B]
Limit DI3
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.4]
[5-0C]
Limit DI4
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
Average timer
The average timer corrects the influence of ambient temperature
variations. The weather-dependent set point calculation is done on
the average outdoor temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
[A.6.4]
[1-0A]
Outdoor average timer:
▪ 0: No averaging (default)
▪ 1: 12 hours
▪ 2: 24 hours
▪ 3: 48 hours
▪ 4: 72 hours
Offset temperature external outdoor ambient sensor
Only applicable in case of an external outdoor ambient sensor is
installed and configured.
You can calibrate the external outdoor ambient temperature sensor.
It is possible to give an offset to the thermistor value. The setting can
be used to compensate for situations where the external outdoor
ambient sensor cannot be installed on the ideal installation location
(see installation).
#
Code
[A.6.5]
[2‑0B]
–5°C~5°C, step: 0.5°C (default: 0°C)
Forced defrost
You can manually start a defrost operation.
The decision to execute the manual defrost operation is made by the
outdoor unit and depends on ambient and heat exchanger
conditions. When the outdoor unit accepted the forced defrost
operation,
will be displayed on the user interface. If
displayed within 6  minutes after forced defrost operation was
enabled, the outdoor unit ignored the forced defrost request.
#
Code
[A.6.6]
N/A
Do you want to start a defrost operation?
Pump operation
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [4‑02] or if
the outdoor temperature drops below the value set by [F‑01]. When
the pump operation is enabled, the pump operation is possible at all
outdoor temperatures.
EWAQ+EWYQ004+005BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P492900-1 – 2017.06
Description
Description
Description
is NOT
Description
#
Code
N/A
[F‑00]
Pump operation:
▪ 0: Disabled if outdoor temperature is
higher than [4‑02] or lower than [F‑01]
depending
operation mode.
▪ 1:
temperatures.
Pump operation during flow abnormality [F‑09] defines whether the
pump stops at flow abnormality or allow to continue operation when
flow abnormality occurs. This functionality is only valid in specific
conditions where it is preferable to keep the pump active when
T
<4°C (pump will be activated for 10 minutes and deactivated after
a
10 minutes). Daikin shall NOT be held liable for any damage
resulting this functionality.
#
Code
N/A
[F‑09]
Pump continue operation when flow
abnormality:
▪ 0: Pump will be deactivated.
▪ 1: Pump will be activated when
T
a
OFF)
INFORMATION
If glycol is present in the system ([E‑0D] set to "1") and a
flow abnormality occurs, then [F‑09] will have NO effect,
and the pump will continue operation (intervals of 20
minutes ON – 4 minutes OFF).
Pump speed limitation
Pump speed limitation [9‑0D] defines the maximum pump speed. In
normal conditions, the default setting should NOT be modified. The
pump speed limitation will be overruled when the flow rate is in the
range of the minimum flow (error 7H).
#
Code
N/A
[9‑0D]
Pump speed limitation
▪ 0: No limitation.
▪ 1~4: General limitation. There is
limitation
required delta  T control and comfort
are NOT guaranteed.
▪ 5~8 (default: 6): Limitation when no
actuators. When there is no heating/
cooling
limitation is applicable. When there is
heating/cooling
speed is only determined by delta T in
relation to the required capacity. With
this
possible
guaranteed.
The maximum values depend on the unit type:
8 Configuration
Description
on
heating/cooling
Possible
at
all
outdoor
Description
<4°C (10 minutes ON – 10 minutes
Description
in
all
conditions.
output,
the
pump
speed
output,
the
pump
limitation
range,
delta
T
and
the
comfort
Installer reference guide
The
is
is
61

Advertisement

Table of Contents
loading

Table of Contents