Daikin EWAQ004BAVP Installer's Reference Manual page 86

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ004BAVP:
Table of Contents

Advertisement

2/7
Field settings table
Breadcrumb
Field code
Setting name
User settings
└─ Preset values
└─ Room temperature
7.4.1.1
Comfort (heating)
7.4.1.2
Eco (heating)
7.4.1.3
Comfort (cooling)
7.4.1.4
Eco (cooling)
└─ LWT main
7.4.2.1
[8-09]
Comfort (heating)
7.4.2.2
[8-0A]
Eco (heating)
7.4.2.3
[8-07]
Comfort (cooling)
7.4.2.4
[8-08]
Eco (cooling)
7.4.2.5
Comfort (heating)
7.4.2.6
Eco (heating)
7.4.2.7
Comfort (cooling)
7.4.2.8
Eco (cooling)
└─ Quiet level
7.4.4
└─ Electricity price
7.4.5.1
[C-0C]
High
[D-0C]
7.4.5.2
[C-0D]
Medium
[D-0D]
7.4.5.3
[C-0E]
Low
[D-0E]
└─ Fuel price
7.4.6
└─ Set weather dependent
└─ Main
└────────────────── Set weather-dependent heating
7.7.1.1
[1-00]
Set weather-dependent heating
7.7.1.1
[1-01]
Set weather-dependent heating
7.7.1.1
[1-02]
Set weather-dependent heating
7.7.1.1
[1-03]
Set weather-dependent heating
└────────────────── Set weather-dependent cooling
7.7.1.2
[1-06]
Set weather-dependent cooling
7.7.1.2
[1-07]
Set weather-dependent cooling
7.7.1.2
[1-08]
Set weather-dependent cooling
7.7.1.2
[1-09]
Set weather-dependent cooling
Installer settings
└─ System layout
└─ Standard
A.2.1.1
[E-00]
Unit type
A.2.1.2
[E-01]
Compressor type
A.2.1.3
[E-02]
Indoor software type
A.2.1.7
[C-07]
Unit control method
A.2.1.8
[7-02]
Number of LWT zones
A.2.1.9
[F-0D]
Pump operation mode
A.2.1.A
[E-04]
Power saving possible
A.2.1.B
User interface location
A.2.1.C
[E-0D]
Glycol present
└─ Options
A.2.2.B
[C-08]
External sensor
└────────────────── Control box
A.2.2.E.1
[E-03]
Backup heater steps
A.2.2.E.2
[5-0D]
BUH type
A.2.2.E.3
[D-01]
Preferential kWh rate
A.2.2.E.5
[C-05]
Contact type main
└────────────────── Option box
A.2.2.F.1
[C-02]
Ext. backup heat src
4P469115-1B - 2017.06
Low ambient temp. for LWT main zone heating
WD curve.
High ambient temp. for LWT main zone heating
WD curve.
Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
Low ambient temp. for LWT main zone cooling
WD curve.
High ambient temp. for LWT main zone cooling
WD curve.
Leaving water value for low ambient temp. for
LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for
LWT main zone cooling WD curve.
Range, step
Default value
R/W
[3-07]~[3-06], step: A.3.2.4
21°C
R/W
[3-07]~[3-06], step: A.3.2.4
19°C
R/W
[3-08]~[3-09], step: A.3.2.4
24°C
R/W
[3-08]~[3-09], step: A.3.2.4
26°C
R/W
[9-01]~[9-00], step: 1°C
45°C
R/W
[9-01]~[9-00], step: 1°C
40°C
R/W
[9-03]~[9-02], step: 1°C
18°C
R/W
[9-03]~[9-02], step: 1°C
20°C
R/W
-10~10°C, step: 1°C
0°C
R/W
-10~10°C, step: 1°C
-2°C
R/W
-10~10°C, step: 1°C
0°C
R/W
-10~10°C, step: 1°C
2°C
R/W
0: Level 1
1: Level 2
2: Level 3
R/W
0,00~990/kWh
0/kWh
R/W
0,00~990/kWh
0/kWh
R/W
0,00~990/kWh
0/kWh
R/W
0,00~990/kWh
0,00~290/MBtu
8,0/kWh
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00]°C, step: 1°C
45°C
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
R/O
0~5
1: Minichiller
R/O
0~1
0: 8
R/O
0: Type 1 (*1)
1: Type 2 (*2)
R/W
0: LWT control
1: Ext RT control
2: RT control
R/O
0: 1 LWT zone
R/W
0: Continuous
1: Sample
2: Request
R/O
0: No
1: Yes
R/W
0: At unit
1: In room
R/W
0: No
1: Yes
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
0: No BUH
1: 1 step
2: 2 steps
R/W
0~5
1: 1P,(1/1+2)
4: 3PN,(1/2)
5: 3PN,(1/1+2)
R/W
0: No
1: Active open
2: Active closed
R/W
1: Thermo ON/OFF
2: C/H request
R/W
0: No
1: Bivalent
2: -
3: -
Installer setting at variance with
default value
Date
Value
(*1) EWYQ*_(*2) EWAQ*

Advertisement

Table of Contents
loading

Table of Contents