Daikin EWAQ004BAVP Installer's Reference Manual page 88

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ004BAVP:
Table of Contents

Advertisement

4/7
Field settings table
Breadcrumb
Field code
Setting name
A.6.3.6.2
[5-0A]
kW limits for DI
A.6.3.6.3
[5-0B]
kW limits for DI
A.6.3.6.4
[5-0C]
kW limits for DI
A.6.3.7
[4-01]
Priority
└─ Averaging time
A.6.4
[1-0A]
└─ Ext amb. sensor offset
A.6.5
[2-0B]
└─ Boiler efficiency
A.6.A
[7-05]
└─ Emergency
A.6.C
└─ Overview settings
A.8
[0-00]
--
--
A.8
[0-01]
A.8
[0-02]
--
A.8
[0-03]
--
A.8
[0-04]
--
A.8
[0-05]
--
A.8
[0-06]
--
A.8
[0-07]
--
A.8
[0-0B]
--
A.8
[0-0C]
--
A.8
[0-0D]
--
A.8
[0-0E]
--
A.8
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
A.8
[1-01]
High ambient temp. for LWT main zone heating WD curve.
A.8
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
A.8
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
A.8
[1-04]
Weather dependent cooling of the main leaving water temperature zone.
A.8
[1-05]
--
A.8
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
A.8
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
A.8
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
A.8
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
A.8
[1-0A]
What is the averaging time for the outdoor temp?
A.8
[2-00]
--
A.8
[2-01]
--
A.8
[2-02]
--
A.8
[2-03]
--
A.8
[2-04]
--
A.8
[2-05]
Room antifrost temperature
A.8
[2-06]
Room frost protection
A.8
[2-09]
Adjust the offset on the measured room temperature
A.8
[2-0A]
Adjust the offset on the measured room temperature
A.8
[2-0B]
What is the required offset on the measured outdoor temp.?
A.8
[3-00]
Is auto restart of the unit allowed?
A.8
[3-01]
--
A.8
[3-02]
--
A.8
[3-03]
--
A.8
[3-04]
--
A.8
[3-05]
--
A.8
[3-06]
What is the maximum desired room temperature in heating?
A.8
[3-07]
What is the mimimum desired room temperature in heating?
A.8
[3-08]
What is the maximum desired room temperature in cooling?
A.8
[3-09]
What is the minimum desired room temperature in cooling?
A.8
[4-00]
What is the BUH operation mode?
A.8
[4-01]
Which electric heater has priority?
A.8
[4-02]
Below which outdoor temperature is heating allowed?
A.8
[4-03]
--
A.8
[4-04]
How to protect the water pipes from freezing
A.8
[4-05]
--
A.8
[4-06]
-- (Do not change this value)
4P469115-1B - 2017.06
Limit DI2
Limit DI3
Limit DI4
Range, step
Default value
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~2
0: None
2: BUH
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
0: Manual
1: Automatic
35°C
45°C
15°C
-10°C
8°C
12°C
35°C
20°C
55°C
60°C
15°C
-10°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
45°C
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
35°C
R/W
0: Disabled
1: Enabled
1
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
5
1
23
60
40
R/W
4~16°C, step: 1°C
16°C
R/W
0: Disabled
1: Enabled
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: No
1: Yes
0
1
4
2
1
R/W
18~30°C, step: A.3.2.4
30°C
R/W
12~18°C, step: A.3.2.4
16°C
R/W
25~35°C, step: A.3.2.4
35°C
R/W
15~25°C, step: A.3.2.4
15°C
R/W
0~2
0: Disabled
1: Enabled
R/W
0~2
0: None
R/W
14~35°C, step: 1°C
25°C
3
R/W
0: Intermittent pump operation
1: Continuous pump operation
2: No protection
0
0/1
Installer setting at variance with
default value
Date
Value
(*1) EWYQ*_(*2) EWAQ*

Advertisement

Table of Contents
loading

Table of Contents