Daikin EWAQ004BAVP Installer's Reference Manual page 89

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ004BAVP:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
A.8
[4-07]
Enable the second step of the backup heater?
A.8
[4-08]
Which power limitation mode is required on the system?
A.8
[4-09]
Which power limitation type is required?
A.8
[4-0A]
--
A.8
[4-0B]
Automatic cooling/heating changeover hysteresis.
A.8
[4-0D]
Automatic cooling/heating changeover offset.
A.8
[4-0E]
Is the installer on site?
A.8
[5-00]
Is backup heater operation allowed above equilibrium temperature during space
heating operation?
A.8
[5-01]
What is the equilibrium temperature for the building?
A.8
[5-02]
Space heating priority.
A.8
[5-03]
Space heating priority temperature.
A.8
[5-04]
--
A.8
[5-05]
What is the requested limit for DI1?
A.8
[5-06]
What is the requested limit for DI2?
A.8
[5-07]
What is the requested limit for DI3?
A.8
[5-08]
What is the requested limit for DI4?
A.8
[5-09]
What is the requested limit for DI1?
A.8
[5-0A]
What is the requested limit for DI2?
A.8
[5-0B]
What is the requested limit for DI3?
A.8
[5-0C]
What is the requested limit for DI4?
A.8
[5-0D]
What type of backup heater installation is used?
A.8
[5-0E]
--
A.8
[6-00]
The temperature difference determining the heat pump ON temperature.
A.8
[6-01]
The temperature difference determining the heat pump OFF temperature.
A.8
[6-02]
--
A.8
[6-03]
What is the capacity of the backup heater step 1?
A.8
[6-04]
What is the capacity of the backup heater step 2?
A.8
[6-05]
--
A.8
[6-06]
--
A.8
[6-07]
--
A.8
[6-08]
--
A.8
[6-09]
--
A.8
[6-0A]
--
A.8
[6-0B]
--
A.8
[6-0C]
--
A.8
[6-0D]
--
A.8
[6-0E]
--
A.8
[7-00]
--
A.8
[7-01]
--
A.8
[7-02]
How many leaving water temperature zones are there?
A.8
[7-03]
--
A.8
[7-04]
--
A.8
[7-05]
Boiler efficiency
A.8
[8-00]
--
A.8
[8-01]
--
A.8
[8-02]
--
A.8
[8-03]
--
A.8
[8-04]
Additional running time for the maximum running time.
A.8
[8-05]
Allow modulation of the LWT to control the room temp?
A.8
[8-06]
Leaving water temperature maximum modulation.
A.8
[8-07]
What is the desired comfort main LWT in cooling?
A.8
[8-08]
What is the desired eco main LWT in cooling?
A.8
[8-09]
What is the desired comfort main LWT in heating?
A.8
[8-0A]
What is the desired eco main LWT in heating?
A.8
[8-0B]
--
A.8
[8-0C]
--
A.8
[8-0D]
--
A.8
[9-00]
What is the maximum desired LWT for main zone in heating?
A.8
[9-01]
What is the mimimum desired LWT for main zone in heating?
A.8
[9-02]
What is the maximum desired LWT for main zone in cooling?
A.8
[9-03]
What is the mimimum desired LWT for main zone in cooling?
A.8
[9-04]
Leaving water temperature overshoot temperature.
A.8
[9-05]
--
A.8
[9-06]
--
A.8
[9-07]
--
A.8
[9-08]
--
(*1) EWYQ*_(*2) EWAQ*
Range, step
Default value
R/W
0: No
1: Yes
R/W
0: No limitation
1: Continuous
2: Digital inputs
R/W
0: Current
1: Power
0
R/W
1~10°C, step: 0,5°C
1°C
R/W
1~10°C, step: 0,5°C
3°C
R/W
0: No
1: Yes
R/W
0: Allowed
1: Not allowed
R/W
-15~35°C, step: 1°C
-4°C
R/W
0: Disabled
1: Enabled
R/W
-15~35°C, step: 1°C
0°C
10
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~5
1: 1P,(1/1+2)
4: 3PN,(1/2)
5: 3PN,(1/1+2)
1
R/W
2~20°C, step: 1°C
2°C
R/W
0~10°C, step: 1°C
2°C
0
R/W
0~10 kW, step: 0,2 kW
3 kW
R/W
0~10 kW, step: 0,2 kW
0 kW
0
0
0
10
0
55°C
45°C
45°C
1
60°C
0°C
2°C
R/O
0: 1 LWT zone
2,5
0
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
1 min
30
0,5
50
R/W
0~95 min, step: 5 min
95 min
R/W
0: No
1: Yes
R/W
0~10°C, step: 1°C
3°C
R/W
[9-03]~[9-02], step: 1°C
18°C
R/W
[9-03]~[9-02], step: 1°C
20°C
R/W
[9-01]~[9-00], step: 1°C
45°C
R/W
[9-01]~[9-00], step: 1°C
40°C
13
10
16
R/W
37~55°C, step: 1°C
55°C
R/W
15~37°C, step: 1°C
25°C
R/W
18~22°C, step: 1°C
22°C
R/W
5~18°C, step: 1°C
5°C
R/W
1~4°C, step: 1°C
1°C
25
55
5
22
5/7
Installer setting at variance with
default value
Date
Value