Top Vent - Horizontal Termination - (continued)
Three Elbows
Note: There MUST be a 25% reduction
in total H when using flex vent except
when using the simple up and out
installation. See Figure 4.9.
Note: Use SLP Series
components only.
WARNING**
Fire Risk.
• When using SLP-HRC-SS termination cap
on top vented fireplaces, a one foot minimum
vertical vent section is required before installing
first elbow.
Figure 4.13
20
V
Minimum**
H
1
1
90 Elbow Only**
1-1/2 ft. 457 mm
1/2 ft.** 152 mm 1-1/2 ft. 457 mm
1-1/2 ft. 457 mm
3 ft.
2-1/2 ft. 762 mm
5 ft.
3-1/2 ft.
1.1 m
7 ft.
4-1/2 ft.
1.4 m
14 ft.
No specific restrictions on this value EXCEPT V
H
2
Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. L • 10/19
Maximum
H
+ H
Maximum
1
2
2 ft.
610 mm
4 ft.
1.2 m
914 mm
6 ft.
1.8 m
1.5 m
10 ft.
3.0 m
2.1 m
14 ft.
4.3 m
4.3 m
14 ft.
4.3 m
H
+ H
MAX. =14 ft. (4.3 m)
1
2
V
+ V
+ H
+ H
MAX. = 40 ft. (12.2 m)
1
2
1
2
+ V
1
** See Warning Below.
V
2
H
V
V
+ V
2
1
*
*
*
*
*
*
+ H
+ H
CANNOT exceed 40 ft. (12.2 m).
2
1
2
1
Minimum
2
*
*
*
*
*
*
V
1