Table of Contents

Advertisement

Quick Links

Models:
SL-550METRO
SL-550METRO-LP
SL-550METRO-BU
• Important operating
a n d m a i n t e n a n c e
instructions included.
WARNING: If the information in these
instructions is not followed exactly, a fi re
or explosion may result causing property
damage, personal injury, or death.
• DO NOT store or use gasoline or other fl am-
mable vapors and liquids in the vicinity of this
or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Immediately call your gas supplier from
a neighbor's phone. Follow the gas sup-
plier's instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed
by a qualifi ed installer, service agency, or the
gas supplier.
This appliance may be installed as an OEM installation in
manufactured home (USA only) or mobile home and must be
installed in accordance with the manufacturer's instructions
and the manufactured home construction and safety standard,
Title 24 CFR, Part 3280 or Standard for Installation in Mobile
Homes, CAN/CSA Z240MH, in Canada.
This appliance is only for use with the type(s) of gas indicated
on the rating plate.
Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12
NOTICE
DO NOT DISCARD THIS MANUAL
• Read, understand and follow
these instructions for safe
installation and operation.
Pour demander un exemplaire en français de ce Manuel
du propriétaire, visitez www.heatnglo.com.
Owner's Manual
Installation and Operation
• Leave this manual with
party responsible for use
and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable
materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the
barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
Installation and service of this appliance should be
performed by qualifi ed personnel. Hearth & Home
Technologies suggests NFI certifi ed or factory trained
professionals, or technicians supervised by an NFI
certifi ed professional.
1

Advertisement

Table of Contents
loading

Summary of Contents for Heat & Glo SL-550METRO-BU

  • Page 1 Technologies suggests NFI certifi ed or factory trained This appliance is only for use with the type(s) of gas indicated professionals, or technicians supervised by an NFI on the rating plate. certifi ed professional. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 2: Congratulations

    00,000 00,000 00,000 MIN. MIN. INPUT INPUT BTUH: BTUH: 00,000 00,000 00,000 00,000 Serial Serial ORIFICE ORIFICE SIZE: SIZE: #XXXXX #XXXXX #XXXXX #XXXXX XXXXXXXX XXXXXXXX (Serie): (Serie): Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 3: Table Of Contents

    E. Junction Box Installation......53 A. Vent Termination Minimum Clearances ....20 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 4 D. Contact Information ......74  = Contains updated information. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 5: Limited Lifetime Warranty

    Firebox and heat exchanger Lifetime All replacement parts 90 Days beyond warranty period See conditions, exclusions, and limitations on next page. 4021-645C 12-29-10 Page 1 of 2 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 6 B. Limited Lifetime Warranty (continued) WARRANTY CONDITIONS: WARRANTY EXCLUSIONS: This warranty is void if: LIMITATIONS OF LIABILITY: 4021-645C 12-29-10 Page 2 of 2 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 7: Listing And Code Approvals

    • A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 8: Requirements For The Commonwealth Of Massachusetts

    VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB- of the installation. STRUCTIONS”. See Gas Connection section for additional Common- wealth of Massachusetts requirements. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 9: User Guide

    - A decorative fi rescreen. DECORATIVE DOORS (NOT SHOWN) SECTION 2.D. FIXED GLASS ASSEMBLY (NOT SHOWN) SECTION 14.F. MANTEL HEARTH CLEAR SPACE SECTION 2.C. Figure 2.1 General Operating Parts Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 10: Clear Space

    For more information refer to the instructions supplied with your decorative door or front. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 11: Lighting Instructions (Ipi)

    For additional information on operating your Hearth & Home Technologies fi replace, please refer to www.fi replaces.com. Final inspection by Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 12: After Fireplace Is Lit

    In an IntelliFire ignition system, the pilot fl ame should turn off when appliance is turned off. continually? Some optional control systems available with IPI models may allow pilot fl ame to remain lit. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 13: Maintenance And Service

    • Carefully set fi xed glass assembly in place on fi replace. Hold glass in place with one hand and secure glass latches with the other hand. • Reinstall door or decorative front. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 14: Maintenance Tasks-Qualifi Ed Service Technician

    • Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided. Figure 3.1 IPI Pilot Flame Patterns Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 15: Installer Guide

    FRAMING HEADED OFF IN CEILING JOISTS (SECTION 8.C) OPTIONAL WALL SWITCH MANTEL AND MANTEL LEG (SECTION 5.D) SURROUND HEARTH EXTENSION GAS LINE (SECTION 11) Figure 4.1 Typical System Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 16: Design And Installation Considerations

    Level Reciprocating saw Flat blade screwdriver Non-corrosive leak check solution 1/2 - 3/4 in. length, #6 or #8 Self-drilling screws Caulking material (300ºF minimum continuous exposure rating) Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 17: Framing And Clearances

    1067 940 1511 1118 1581 1232 1746 NOTICE: A minimum of 1/2 inch bottom door clearance is required on all SL-550METRO installations. Figure 5.1 Appliance Locations Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 18: Constructing The Appliance Chase

    * Adjust framing dimensions for interior sheathing (such as sheetrock) ** NOTICE: Appliance must be raised off fl oor or hearth a minimum of 1/2 inch when using the Modern Front. Figure 5.2 Clearances to Combustibles Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 19: Mantel And Wall Projections

    See Figure 5.7. 11-1/2 IN.. 1 IN. 1 IN. 1/2 IN. = NON-COMBUSTIBLE ZONE Figure 5.7. Combustible Tape Area Figure 5.4 Non-Combustible Zone Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 20: Termination Locations

    Over 18/12 to 20/12 ..........7.5 Over 20/12 to 21/12 ..........8.0 * 3 foot minimum in snow regions Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 21 2 sides beneath the fl oor. venting system does not meet these requirements. Figure 6.3 Minimum Clearances for Termination • Vinyl protection kits are suggested for use with vinyl siding. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 22: Vent Information And Diagrams

    DVP12A 3 to 12 76 to 305 DVP12MI 3 to 12 76 to 305 DVP24MI 3 to 24 76 to 610 Figure 7.2 DVP Pipe Effective Length Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 23: Use Of Flex Vent

    However, the vent at- 1 in. tachment point and the fi restop loca- CLEARANCE tion are considered to be supports. Figure 7.3 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 24: Vent Diagrams

    V + H MAX. = 40 ft. (12.2 m) WARNING Fire Risk. • A one foot minimum vertical vent section is required before installing fi rst elbow. Figure 7.4 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 25 MAX. = 40 ft. (12.2 m) WARNING Fire Risk. • A one foot minimum vertical vent section is required before installing fi rst elbow. INSTALLED HORIZONTALLY Figure 7.5 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 26 + H cannot exceed 40 ft. (12.2 m) WARNING Fire Risk. • A one foot minimum vertical vent section is required before installing fi rst elbow. Figure 7.6 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 27 fl ame height. If the vent confi guration has a total vertical of 15-60 feet, an exhaust restrictor may be need- ed. The exhaust restrictor can be located in the appliance manual bag. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 28 (see Figure 7.3). WARNING Fire Risk. • A one foot minimum vertical vent section is required before installing fi rst elbow. Figure 7.9 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 29 (see Figure 7.3). WARNING Fire Risk. • A one foot minimum vertical vent section is required before installing fi rst elbow. INSTALLED HORIZONTALLY Figure 7.10 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 30 Note: There MUST be a 25% reduction in total H when using fl ex vent except when using the simple up and out installation (see Figure 7.3). Figure 7.11 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 31 Figure 7.12 Rear Vent - Horizontal Termination = 9 in. (229 mm) Maximum One 45º Elbow Note: Use DVP Series components only. Figure 7.13 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 32: Rear Vent - Horizontal Termination

    6 ft. 1.8 m 13-1/2 ft. 4.1 m MAX. = 7-1/2 ft. (2.3 m) MAX. = 13-1/2 ft. (4.1 m) MAX. = 40 ft. (12.2 m) Figure 7.15 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 33 2.0 m 3 ft. 914 mm H MAX. = 6-1/2 ft. (2 m) V + H+ H MAX. = 40 ft. (12.2 m) INSTALLED HORIZONTALLY Figure 7.17 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 34 MAX. = 14-1/2 ft. (4.4 m) MAX. = 40 ft. (12.2 m)  MAX. = 40 ft. (12.2 m) Note: Use DVP Series components only. Figure 7.18 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 35: Coaxial To Colinear Venting

    CAUTION! DO NOT use any fl ue restrictor when vent- ing with the DV-46DVA-GCL adapter and LINK-DV30B kit. This may result in poor fl ame appearance, sooting, pilot malfunction, or overheating. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 36: Rear Vent

    3.05 m 0 ft. 0 mm Minimum 10 ft. 3.05 m Maximum 40 ft. 12.2 m 2 ft. 610 mm Maximum 40 ft. 12.2 m Figure 7.21 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 37: Vent Clearances And Framing

    * Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) inch (25.4 mm) above the center of the horizontal vent pipe. Figure 8.2 Wall Penetration Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 38: Install The Ceiling Firestop

    BEFORE OR AFTER INSTALLATION OF VENT SYSTEM 3 FASTENERS PER SIDE CEILING FIRESTOP CEILING FIRESTOP INSTALLED BELOW CEILING INSTALLED ABOVE CEILING Figure 8.4 Installing the Attic Shield Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 39: Install Attic Insulation Shield

    • Bend all tabs inward 90º around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 40: Appliance Preparation

    For rear vent, see Section 9.B. Figure 9.6 Remove the seal cap. WARNING! Risk of Fire! Do not remove heat shield. El- evated header temperatures may cause a fi re. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 41: Rear Vent

    Note: Once the vent cap has been removed, it cannot be reattached. Figure 9.13 Cut the metal retaining band and fold the sides out. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 42: Securing And Leveling The Appliance

    Figure 9.17 Proper Positioning and Securing of an Appliance up against the appliance and over the tabs. Use two self- tapping screws to secure gasket to outer wrap. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 43: Installing Vent Pipe (Dvp And Slp Pipe)

    fl ue at the horizontal elbow joint to prevent the elbow from rotating. Use screws no longer than 1/2 in. (13 mm). If predrilling screw holes, DO NOT penetrate inner pipe. INCORRECT Figure 10.4 Seams Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 44: Assemble Vent Sections (Slp Pipe Only)

    • Only outer pipes are sealed, sealing the inner fl ue is not required. • All unit collar, pipe, slip section, elbow and cap outer fl ues shall be sealed. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 45: Secure The Vent Sections

    Figure 10.10 Rotate Seams for Disassembly connection point to appliance. 120º Figure 10.11 Align and Disassemble Vent Sections Figure 10.8 Securing Vertical Pipe Sections 120º Figure 10.9 Securing Horizontal Pipe Sections Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 46: Install Decorative Ceiling Components (Slp Only)

    fl aps and the roof. Figure 10.13 WARNING! Risk of Fire! Clean out ALL materials from inside the support box and complete the vertical vent run and termination. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 47: Install Metal Roof Flashing

    • Caulk the overlap seam of any exposed pipe sections that are located above the roof line. Figure 10.17 Assembling the Storm Collar Around the Pipe Figure 10.17 Assembling the Storm Collar Around the Pipe Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 48: Install Vertical Termination Cap

    • Once the pipe section and the termination cap have been connected, slide the wall thimble up to the interior wall surface and attach with screws provided. See Figure 10.19. Figure 10.19 Wall Thimble Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 49: Install Horizontal Termination Cap (Dvp And Slp Pipe)

    DVP-TRAP2 can adjust 4 in. (5-3/8 to 9-3/8) DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8) DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2) * Not approved for Central America Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 50: Gas Information

    For elevations above 2000 feet, mm) control valve inlet. open burner aeration shutter 1/16 in. for every 2000 feet. • If substituting for these components, please consult local codes for compliance. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 51: Electrical Information

    Remove batteries before using the transformer, and unplug the transformer before installing the batteries. Battery polarity must be correct or module damage will occur. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 52 3 VAC WHITE GROUND TO FIREPLACE PLUG IN CHASSIS WIRES BATTERY PACK (TO BROWN) REMOTE PLUG IN VALVE Figure 12.2 Intellifi re Ignition Wiring Diagram with Remote Receiver Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 53: Junction Box Installation

    Copper ground attached GRN wire to GRN screw with inside box GRN wire NOTICE: DO NOT wire 110 VAC to wall switch. Figure 12.3 Junction Box Detail Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 54: Finishing

    Figure 13.2 Step 3. Crease fl aps on left and right sides of splatter guard Figure 13.5 using the scored line as the guide. See Figure 13.3. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 55 Carefully grab splatter guard on or near the vertical center on the left and right sides. Pull outward gently, but fi rmly, Figure 13.8 taking care not to tear or remove the inserted tabs. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 56: Mantel And Wall Projections

    Combustible tape may be placed up to one inch into the non-combustible zone. See Figure 13.16. 11-1/2 IN.. 1 IN. 1 IN. 1/2 IN. Figure 13.16 Combustible Tape Area Figure 13.13 Non-Combustible Zone Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 57: Facing Material

    If desired fi nishing includes a painted wall, 100% acrylic latex with compatible primer is recommended around this appliance. Oil-based or standard acrylic paints may dis- color due to heat exposure. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 58 Modern front only. Figure 13.19 Inside Fit Door 1 in. MAX DOOR FINISHING MATERIAL (TOP EDGE) 34-1/2 IN. 37-1/4 IN. Figure 13.18 Modern Door Clean Finishing-Overlap Fit Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 59: Appliance Setup

    Shutter Settings Models ULPG BUTANE SL-550METRO 3/16 in. 1/4 in. 1/4 in. 5/16 in. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 60: Troubleshooting

    Verify module is securely grounded to metal chassis of appliance. D. Module voltage output / Valve/Pilot Verify battery voltage is at least 2.7 volts. Replace batteries if volt- solenoid ohms readings. age is below 2.7. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 61 ON position. If there is no spark at “I” terminal module must be replaced. If there is a spark at “I” terminal, module is fi ne. Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 62: Reference Materials

    Inches Millimeters Location Inches Millimeters 8-13/16 31-1/8 16-5/16 27-3/16 18-1/16 25-3/4 31-1/8 12-7/8 3-9/16 15-7/8 6-7/8 6-5/8 23-3/8 2-3/16 42-5/8 1083 1245 30-1/16 Figure 16.1 Appliance Dimensions Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 63: Vent Components Diagrams

    14 in. (356 mm) 5 in. 12 in. (127 mm) (305 mm) 6 in. (152 mm) DVP-HVS (Vent Support) DVP-WS (Wall Shield Firestop) Figure 16.2 DVP vent components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 64 9-3/8 in. 12 in. Trap2 Effective 137 mm 238 mm (305 mm) Length DVP-TRAP Horizontal Termination Cap DVP-TRAP2 DVP-TRAP1 DVP-TRAPK2 DVP-TRAPK1 DVP-HPC1 DVP-HPC2 Figure 16.3 DVP vent components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 65 Cap Shield DVP-TRAPFL Flashing 13-7/8 in. 9-1/2 in. (352 mm) (241 mm) 14 in. (356 mm) DVP-HSM-B Extended Heat Shield DRC-RADIUS Cap Shield Figure 16.4 DVP vent components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 66 8-3/4 in. 7-3/4 to 10-3/8 in. (222 mm) (197 to 264 mm) 1-5/8 in. DVP-FBHT (41 mm) FireBrickTermination Cap DVP-HPC High Performance Cap Figure 16.5 DVP vent components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 67 (381 mm) 267 mm 10-7/8 in. 276 mm SLP-HRC-SS SLP-HRC-ZC-SS HORIZONTAL TERMINATION CAP DVP-TB1 DVP-TB1 SL-2DVP SLP90 ASSEMBLY DVP-TB1 HORIZONTAL TERMINATION CAP Figure 16.7 SLP Series Vent Components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 68 1-1/2 in. 12 in. 5-1/2 in. 220 mm 38 mm 305 mm 146 mm SLP-WS SLP-FS Wall Shield Firestop Ceiling Firestop Figure 16.8 SLP Series Vent Components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 69 356 mm 192 mm 16 in. SLP-FLEX-TRAP (406 mm) Horizontal Termination Kit PVK-80 (For use with IPI and DSI appliances only.) Figure 16.9 SLP Series Vent Components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 70 12-1/2 IN. (318 mm) SLP Low Profi le Cap COAXIAL to COLINEAR VENTING LINK-DV30B DVP-2SL DV-46DVA-GCL Flex Liner Kit Adapter Coaxial/Colinear Appliance Connector Figure 16.10 Vent Components Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 71: Service Parts

    Heat Shield, Header 2118-120 Heat Shield, Junction Box 2185-117 Non-combustible Board 2185-110 Touch Up Paint TUP-GBK-12 Valve Plate Cover 2188-101 Additional service part numbers appear on following page. 8/12 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 72 Jumper Wires, 2 in, male to male Conversion Kit NG NGK-550METRO Conversion Kit LP LPK-550METRO Pilot Orifi ce NG 593-528 Pilot Orifi ce LP 593-527 Regulator NG NGK-DXF Regulator LP LPK-DXF Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 73 NGK-550METRO Conversion Kit, P & B LPK-550METRO Pilot Orifi ce, N 593-528 Pilot Orifi ce, P & B 593-527 Regulator, N NGK-DXF Regulator, P & B LPK-DXF Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...
  • Page 74: Contact Information

    5647340, 5890485, 5941237, 5947112, 5996575, 6006743, 6019099, 6053165, 6145502, 6170481, 6374822, 6484712, 6601579, 6769426, 6863064, 7077122, 7098269, 7258116, 7470729 or other U.S. and foreign patents pending. 2000-945 Printed in U.S.A. - Copyright 2012 Heat & Glo • SL-550METRO, SL-550METRO-LP, SL-550METRO-BU • 2185-900 Rev. Q • 8/12...