ing 12 or 13 until the LCD display shows
the message Cod, indicating entry into
"parameter Cod" (Figure 9.20), and then
displays three dashes "- - -".
Figure 9.20
• Press the 16 button to set "1 - -", then
press 12 to confirm the 1 and go to the
next segment.
• Press the 16 button to set "1 9 -", then
press 12 to confirm the 9 and go to the
next segment.
• Press the 16 button to set "1 9 8", then
press 12 to confirm the 8 and go back to
the list of parameters.
• The code A01 appears on the display, in-
dicating entry into "parameter A01" (Fig-
ure 9.21).
Figure 9.21
• By using buttons 15 or 16 (Figure 9.18) it
is possible to modify the value of parame-
ter A01 (Figure 9.22).
00 = Methane gas (G20)
01 = Propane gas - LPG (G31)
Figure 9.22
- 60 -
MAINTENANCE
RESET
bar
RESET
bar
RESET
bar
• Press 12 or 13 (Figure 9.18) to confirm the
value entered and return to the list of pa-
rameters (Figure 9.21).
• Press 12 and hold until the LCD display
shows the code A02, indicating entry into
"parameter A02" (Figure 9.23).
Figure 9.23
• By using buttons 15 or 16 (Figure 9.18) it
is possible to modify the value of param-
eter A02:
01 = high temperature (50/80°C)
02 = low temperature (28/55°C)
• Press 12 or 13 (Figure 9.18) to confirm the
value entered and return to the list of pa-
rameters (Figure 9.23).
• Press button 13 and hold until the LCD
display shows the code A21, indicating
entry into "parameter A21" (Figure 9.24).
Figure 9.24
• By using buttons 15 or 16 (Figure 9.18) it
is possible to modify the value of parame-
ter A21 (Figure 9.25).
00 = Room thermostat
01 = Remote control
RESET
bar
RESET
bar