• Press the 16 button to set "1 - -", then
press 12 to confirm the 1 and go to the
next segment.
• Press the 16 button to set "1°9 -", then
press 12 to confirm the 9 and go to the
next segment.
• Press the 16 button to set "1°9°8", then
press 12 to confirm the 8 and go back to
the list of parameters.
• The code A01 appears on the display, in-
dicating entry into "parameter A01" (Fig-
ure 8.5).
Figure 8.5
• By using buttons 15 or 16 (Figure 8.2) it is
possible to modify the value of parameter
A01 (Figure 8.6).
00 = Methane gas (G20)
01 = Propane gas - LPG (G31)
Figure 8.6
• Press 12 or 13 (Figure 8.2) to confirm the
value entered and return to the list of pa-
rameters (Figure 8.5).
• Press the 17 button (Figure 8.2) to exit
"programming mode".
• Calibrate the gas valve according to the
instructions in section "CHECKING THE
GAS SETTING" on page 48.
- 54 -
GAS CONVERSION
RESET
bar
RESET
bar
• Reposition the control panel and reas-
semble the front panel of the body.
• Apply the label indicating the type of gas
and the pressure value for which the unit
is set. The self-adhesive label is included
in the conversion kit.