Controller Specifications And Dimensions - Trane Symbio 210 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Controller Specifications and Dimensions

Controller storage, operating, and compliance information
Table 1.
Storage
Operating
Environmental Rating (Enclosure): NEMA 1
Agency Compliance
• UL916 PAZX- Open Energy Management Equipment
• UL94-5V Flammability
• UL2043 Plenum Rated (Plastic enclosure versions without actuators only)
• CE Marked
• FCC Part 15, Subpart B, Class B Limit
• VCCI-CSPR 32:2016
• CAN ICES-003(B)/NMB-003(B)
• Communications BACnet MS/TP, BACnet IP, or BACnet Zigbee (Air-Fi).
• The Symbio 210 is BACnet Testing Laboratory (BTL) certified to revision 15 of the ASHRAE BACnet-135 standard as a Building Controller (BC)
profile device.
• The European Union (EU) Declaration of Conformity is available from your local Trane® office.
Figure 1.
BAS-SVX084A-EN
Temperature: -67°F to 203°F (-55°C to 95°C)
Humidity: 5% to 95% (non-condensing)
Temperature: -40°F to 122°F (-40°C to 50°C)
Humidity: 5% to 95% (non-condensing)
20-4–27.6 Vac, (24 Vac ±15% nominal, 50–60 Hz, 10.5 VA). See
Power:
transformer sizing details.
Pollution: U.L. 840: Degree 2
Dimensions (with actuator)
Overview
Table 5, p. 14
for
7