Troubleshooting Procedures; Symbio 210 Controller Failure - Trane Symbio 210 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Table 15. Controller diagnostics (continued)
Diagnostic
Freeze protection active (ventilation flow
control)
Thumbwheel in * position (single star position) Minimum airflow
Thumbwheel in ** position (double star position) Maximum airflow
Normal
(a) If system mode is heat or auto with a warm or hot supply air temperature
(b) When a temperature sensor fails after being valid, the controller generates a diagnostic to indicate the sensor loss condition. The controller automatically
clears the diagnostic once a valid sensor temperature value is present (non-latching diagnostic).

Troubleshooting Procedures

Symbio 210 Controller Failure

Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
In the event the Symbio 210 controller fails, check the following:
BAS-SVX084A-EN
Air Valve
Closed
Normal
Check for incorrect supply voltage or no voltage. Verify that Symbio 210 is properly grounded
through one leg of transformer or with jumper to ground.
– Check Marquee LED for the following:
– Displays solid green when the Symbio 210 controller is powered and operating
normally.
– Displays solid red when the Symbio 210 controller is powered, but represents low
power or a malfunction.
– If marquee LED displays solid red, check incoming power. Measure the power input to
the Symbio 210 controller on XFMR 24 Vac input and
The supply voltage should be between 20.4 to 27.6 Vac (24 Vac cataloged). However,
voltages at either extreme may result in system instability.
– If no voltage, check up stream of controller to see were voltage has been interrupted.
Refer to the section,
Check for short.
– Remove all wires from controller except incoming power.
– Check device using Tracer TU service tool to see if the Symbio 210 controller is operating
properly. If it does operate properly check, inputs/outputs for a short.
– If controller still fails, replace controller.
Note: For Instructions on how to use Tracer TU, refer to the Tracer TU Online Help and to
the Tracer TU Service Tool User Guide (BAS-SVU047).
Check for alarms or diagnostics with Tracer TU service tool.
Fan
Off
Normal
Normal
Normal
WARNING
"Appendix: Typical Trane Factory Wiring Diagrams," p.
Troubleshooting
Reheat
Off
Normal
Normal
Normal
.
73.
55