Guidelines - Trane Symbio 210 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Wiring Installation
Note: If the sequence completes as described, the controller is properly booted and ready for the

Guidelines

Important:
Table 5.
Calculating actual VA requirements
Item
Symbio 210 Board
24 Vdc Supply
Binary Outputs (TRIAC)
14
b. The Status LED illuminates solid green when the controller is finished booting.
application code. If the Status LED flashes red, a fault condition exists.
Use 18 AWG copper wire (recommended) for power and connect to terminals XFRM 24 Vac and
.
Use U.L. listed, Class 2 power transformer, 20.4 to 27.6 Vac (24 Vac nominal).
Size the transformer to provide adequate power to the Symbio 210 controller (24 VA maximum)
and outputs (maximum 12 VA for each binary output).
A dedicated 24 Vac, Class 2 transformer is recommended to power the Symbio 210
controller. When powering multiple controllers from one transformer, polarity must
be maintained. Terminal 24 Vac is designated positive (+) and terminal
negative (-) to the unit casing ground. It is important to include power consumption
in the calculations.
The power consumption for cooling-only Series F Models (VariTrac™ and VariTrane™) is up to
26 VA. Refer to
Table 5, p. 14
Sub
Symbio 210 (No I/O)
Symbio 210e (No I/O)
(a)
3 x AI
(a)
2 x UI
1 x PI
1 x BI
2 x AO
5 x BO (TRIAC)
Subtotal for Symbio 210 with all I/O used
Subtotal for Symbio 210e with all I/O used
(b)
200 mA
IMC and I/O
250 mA USB Host
Total for Symbio 210 fully loaded
Total for Symbio 210e fully loaded
5 x BO (TRIAC)
for information about calculating actual VA requirements.
VA Draw Per I/O (24 Vac)
0 VA per AI
0 VA per UI
0.3 VA per PI
0.1 VA per BI
1.1 VA Per AO
0.1 VA Per TRIAC (No Load)
1 VA Per 20 mA DC
3 VA Per USB Host
0.5 A @ 24 Vac = 12 VA per BO
is
Maximum Total VA Draw (24
Vac)
8 VA
9.5 VA
0 VA
0 VA
0.3 VA
0.1 VA
2.2 VA
0.5 VA
11.1 VA
12.6 VA
10.0 VA
3.1 VA
24.2 VA
25.7 VA
60.0 VA