Supply/Discharge Air Temperature Sensor Failure - Trane Symbio 210 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Troubleshooting

Supply/Discharge Air Temperature Sensor Failure

Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual
could result in exposure to electrical, mechanical or other potential safety hazards. Always
refer to the safety warnings provided throughout this manual concerning these procedures.
When possible, disconnect all electrical power including remote disconnect and discharge all
energy storing devices such as capacitors before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized. When necessary to work
with live electrical components, have a qualified licensed electrician or other individual who
has been trained in handling live electrical components perform these tasks. Failure to follow
all of the recommended safety warnings provided, could result in death or serious injury.
In the event that the Symbio 210 controller reports an incorrect or failed discharge or supply air
temperature, check the following:
62
Ensure the Symbio 210 controller has been configured for the input and the point has not been
placed out of service.
Discharge or supply air temperature is higher or lower than what the Symbio 210 controller
reads.
Check the location and installation of the sensor. Change the calibration factor in the Symbio
210 controller setup screens.
Note: If sensor is off more than ± 2 degrees continue to the next bullet.
Check sensor wiring for the correct connections.
Defective sensor.
– Disconnect the sensor terminal plug from the Symbio 210 controller and using an
ohmmeter, measure the resistance across the sensor wires. Compare the resistance to
temperature (refer to
temperature within ± 2 degrees near those measured with an accurate temperature
measuring device. If the measured resistance does not correspond, replace the sensor.
Defective wiring or defective Symbio 210 controller.
– Verify that the Symbio 210 controller is outputting 2.6–3.0 Vdc. This can be performed by
disconnecting the wires on the Symbio 210 controller on terminals AI3 and
discharge air temperature sensor and measuring the Vdc. It should be 5 Vdc. If there is 2.6–
3.0 Vdc at the Symbio 210 controller, the wires going to the zone are OPEN. If 5 Vdc is not
present, check the incoming power to the Symbio 210 controller on XFMR 24 Vac input and
. It should measure 24 Vac ± 15%. If the proper voltage is measured at XFMR 24 Vac input
, and there is no voltage at AI4 and
for supply air temperature sensor, replace the Symbio 210 controller.
WARNING
Table 16, p.
58). The resistance measured should correspond to a
for discharge air temperature sensor or AI5 and
for a
BAS-SVX084A-EN

Advertisement

Table of Contents
loading

Table of Contents