Event Annunciation - Siemens FIREFINDER-XLS Operation Manual

Table of Contents

Advertisement

CHAPTER 3 |

Event Annunciation

Technical Manuals Online! - http://www.tech-man.com
Alarm(s) 0
Sup(s) 0
Security(s) 0
)
WALKTEST 3:59
First Floor Reception Area
10:53
DLC@1
In Walktest
Acknowledge
Troubles
Figure 3-31
Walktest Time Remaining In Alert Mode
Upon termination, whether manual or automatic, Alarm events are reported for all
devices remaining in alarm after the walktest is terminated.
In order to ensure that devices return to normal state before the test ends, do not
perform any Walktest activations for at least 5 minutes prior to the expiration of the
Walktest or the planned cancellation time. In order to reduce the possibility of a
false alarm, ensure that all tested devices are cleared prior to terminating the
Walktest.
The Walktest is automatically terminated if an Alarm or Supervisory occurs during
the test to a device that is not being walktested.
After the Walktest is terminated for any reason, the "Walktest Activated" trouble will
remain posted IN on the PMI and full detection functionality will not be restored until
the panel is reset.
Walktest events are annunciated on the PMI in a pop-up box (See Figure 3-32). The
user may press Close on the touch screen to clear the box, or the box will time out
after 30 seconds. When bells are enabled, the audibles will sound for five seconds.
(When Group Bells are activated, only audibles in the group being tested will sound.
When All Bells has been selected, all audibles are activated when a device is
walktested.)
**********WALKTEST**********
Alarm
1st Flr Hallway 2
:5-7
HFP11
Close
Figure 3-32
Walktest Pop-up Box
firealarmresources.com
PMI OPERATION MANUAL
Trouble(s) 1
Reset
System
MAINTENANCE MODE
3-19