OPERATION
− Enter the password
− Select "(97) IO Configuration" and press the ● button
− With the ▲ / ▼ keys change the value following what is in
the following table and press the ● key:
Model
AR 399 SE
AR 500 SE
9
(*) Par. 126 = 10 (DEFAULT 6)
− Press the ▼ key, select "(98) Appliance Settings" and press
the ● key
Appliance Configuration
"
(97) IO Configuration
"
"
(98) Appliance Settings
"
"
Configuration Confirmed
"
− With the ▲ / ▼ keys change the value following what is in
the following table and press the ● key:
Model
AR 399 SE
AR 500 SE
− Press the ▼ key, select "Config. Confirmed" and press the
● key
− With the ▲ / ▼ keys change the value to "Yes" and press
the ● key
Appliance Configuration
"
(97) IO Configuration
"
"
(98) Appliance Settings
"
"
Configuration Confirmed
"
At this point the systems starts an application update process.
Once this is finished, the menu "Settings" appears on the menu.
− Press ◄ until you return to the home screen
An error message is displayed for a few seconds and then the dis-
play returns to its normal state.
Par. 97
NG
LPG
22
22
22
22
"
1
2
No
"
"
"
Par. 98
NG
LPG
83
84
82
82
"
1
4
Yes
"
"
"