PRODUCT DESCRIPTION
2.12 Pumps
The Array AR 399 SE and Array AR 500 SE are equipped with a
built-in circulator with integrated check valve.
9
CAUTION: During the first start-up, and at least once a year, the
rotation of the circulator shaft should be checked as, espe-
cially after long periods of not being operated, deposits and/
or residuals could impede its free rotation.
9
CAUTION: Before loosening or removing the circulator cap, pro-
tect the electric devices located underneath from any water
that exits.
0
STOP: It is prohibited to operate the circulators without water.
2.13 Water circuit
6
5
4
3
2
10
RI
1
Heat exchanger
2
Pump
3
Check valve
4
Drain cock
5
Minimum Water Pressure
Switch (set to 7 psi/0.5
bar)
6
NTC return sensor
Fig. 5 Water circuit
1
11
7 8 9
MI
7
Safety water high-limit
thermostat temperature
sensor
8
NTC flow sensor
9
Automatic air vent
10 Flow-meter
11
LWCO
MI Central heating supply
RI Central heating return
2.14 Positioning of the temperature sensors
1
Limit thermostat temperature
2
Water temperature sensor
3
Return temperature sensor
4
Flue sensor
4
Fig. 6 Positioning of the temperature sensor
14
1
2
3