8301-091 Dust (Particulate) Sensor - Bard FUSION-TEC HR35BPA Service Instructions Manual

Wall-mount
Table of Contents

Advertisement

8301-091 Dust (Particulate) Sensor

The following measurements are taken across V+ and GND on Dust Sensor Alarm
Dust
µg/m3
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Manual 2100-694B
Page
52 of 62
8301-073 Sensor: Dust/Volts
Signal
Dust
Vdc
µg/m3
0.10
34
0.15
35
0.20
36
0.25
37
0.30
38
0.35
39
0.39
40
0.44
41
0.49
42
0.54
43
0.59
44
0.64
45
0.69
46
0.74
47
0.79
48
0.84
49
0.88
50
0.93
51
0.98
52
1.03
53
1.08
54
1.13
55
1.18
56
1.23
57
1.28
58
1.33
59
1.37
60
1.42
61
1.47
62
1.52
63
1.57
64
1.62
65
1.67
66
1.72
67
TABLE 18
Signal
Vdc
1.77
1.82
1.86
1.91
1.96
2.01
2.06
2.11
2.16
2.21
2.26
2.31
2.35
2.40
2.45
2.50
2.55
2.60
2.65
2.70
2.75
2.80
2.84
2.89
2.94
2.99
3.04
3.09
3.14
3.19
3.24
3.29
3.33
3.38
Dust
Signal
µg/m3
Vdc
68
3.43
69
3.48
70
3.53
71
3.58
72
3.63
73
3.68
74
3.73
75
3.78
76
3.82
77
3.87
78
3.92
79
3.97
80
4.02
81
4.07
82
4.12
83
4.17
84
4.22
85
4.27
86
4.31
87
4.36
88
4.41
89
4.46
90
4.51
91
4.56
92
4.61
93
4.66
94
4.71
95
4.76
96
4.80
97
4.85
98
4.90
99
4.95
100
5.00