FUSION-TEC HR Series Wall-Mount Unit Control Board Terminals
Terminal
Rx+/Tx+
Communication
Rx-/Tx-
Communication
DI1
DI2
Dirty Filter Switch
DI3
Compressor Alarm Relay
DI4
Power Loss Relay (if equipped)
DI5
DI6
Damper Blade Switch
DI7
GND
Digital Ground
B1
Liquid Line Temperature Sensor
B2
Outdoor Air Temperature Sensor
B3
Return Air Temperature Sensor
B4
Supply Air Temperature Sensor
B5
Outdoor Humidity Sensor
B6
Dust Sensor Board
B7
Suction Temperature Sensor
GND
Analog Ground
+VDC
24VDC to Outdoor Humidity Sensor
B8
Liquid Pressure Transducer
B9
Suction Pressure Transducer
GND
Y1
Blower Motor Signal
Y2
Damper Actuator Signal
Y3
Condenser Motor Signal
C1
NO1
NO2
To Compressor Staging Solenoid
NO3
C2
NO4
Stage 1 Heating
NO5
NO6
Dust Sensor Enable
NO7
Unit Fail (Open on Fail)
C7
Unit Fail Common
NC7
Unit Fail (Close on Fail)
C8
NO8
Dirty Filter Light
NO9
GO
24VAC Common
G
TABLE 12
Function
Unit Disable
Not Used
Airflow
Ground
24VAC+
To CCM "Y"
Not Used
24VAC+
Not Used
24VAC+
Not Used
24VAC Hot
Type
Digital Input
Digital Input
Digital Input
Digital Input
Digital Input
Digital Input
Analog Input
10K Ohm Curve J
Analog Input
10K Ohm Type III (AN)
Analog Input
10K Ohm Curve J
Analog Input
10K NTC Thermistor
Analog Input
Analog Input
Analog Input
10K Ohm Curve J
Analog Input
.5VDC – 4.5VDC
Analog Input
.5VDC – 4.5VDC
Analog Output
0 – 10VDC
Analog Output
0/2 – 10VDC
Analog Output
0 – 10VDC
Power
Relay Output
Relay Output
Power
Relay Output
Relay Output
Relay Output
Relay Output
Common
Relay Output
Power
Relay Output
Relay Output
Form
N/C
N/C
N/C
N/C
N/C
N/C
0-5VDC
Manual 2100-694B