8301-057 Blower Status Switch/Dirty Filter Switch; Figure 61 8301-057 Air Differential Switch Terminals - Bard FUSION-TEC HR35BPA Service Instructions Manual

Wall-mount
Table of Contents

Advertisement

8301-057 Blower Status Switch/Dirty Filter Switch

Terminals
1 − Normally Closed
2 − Normally Open
3 − Common
NOTE: Contact position is in resting
state.
Unit
Filter Blockage %
Switch Static Setting
HR35BP*
(Default) High S/T
Evaporator Airflow %
Switch Static Setting
HR35BP*
Standard
Evaporator Airflow %
Switch Static Setting
HR36BP*
(Default) High S/T
Evaporator Airflow %
Switch Static Setting
HR36BP*
Standard Airflow
Evaporator Airflow %
Switch Static Setting
HR58BP*
(Default) High S/T
Evaporator Airflow %
Switch Static Setting
HR58BP*
Standard Airflow
Evaporator Airflow %
* Bard recommends filter switch be set at 50% filter blockage or less. Higher settings may significantly hinder unit
performance.
Manual 2100-694B
Page
48 of 62
FIGURE 61
8301-057 Air Differential Switch Terminals
P2
TABLE 16
8301-057 Differential Air Pressure Switch Settings
0%
10%
0.65
0.70
100%
99.0%
0.40
0.43
100%
99.7%
0.12
0.12
100%
99.3%
0.12
0.12
100%
99.3%
0.40
0.50
100%
98.7%
0.30
0.35
100%
99.8%
P1
P1: Hose Connected
P2: Stub Connected
20%
30%
40%
0.75
0.85
0.95
97.0%
96.4%
95.5%
0.45
0.50
0.55
98.7%
96.8%
96.0%
0.12
0.20
0.20
99.4%
98.7%
96.5%
0.12
0.12
0.20
99.4%
98.8%
97.3%
0.60
0.70
0.75
98.1%
97.5%
91.7%
0.40
0.45
0.50
99%
98.5%
96.8%
50%*
60%
70%
1.05
1.25
1.50
92.7%
88.1%
80.6%
0.65
0.75
0.90
94.4%
91.6%
85.2%
0.35
0.35
0.40
92.1%
91.3%
87.9%
0.20
0.20
0.30
91.5%
89.8%
88.3%
0.80
0.90
1.00
81.3%
79.1%
78.6%
0.65
0.70
0.90
89.9%
84%
82.2%