Figure 33 Dirty Filter Switch And Filter Indicator Light - Bard FUSION-TEC HR35BPA Service Instructions Manual

Wall-mount
Table of Contents

Advertisement

Unit
Filter Blockage %
Switch Static Setting
HR35BP*
(Default) High S/T
Evaporator Airflow %
Switch Static Setting
HR35BP*
Standard
Evaporator Airflow %
Switch Static Setting
HR36BP*
(Default) High S/T
Evaporator Airflow %
Switch Static Setting
HR36BP*
Standard Airflow
Evaporator Airflow %
Switch Static Setting
HR58BP*
(Default) High S/T
Evaporator Airflow %
Switch Static Setting
HR58BP*
Standard Airflow
Evaporator Airflow %
All units tested equipped with MERV 8 filters. Appropriate supply (SG) and return (RG) grilles installed during testing.
Pressure switch adjustment may be necessary due to variations in filter type, installation and room pressure.
Bard recommends filter switch be set at 50% filter blockage or less. Higher settings may significantly hinder unit
performance.
ADJUSTMENT
INDICATOR ARROW
ADJUSTMENT
KNOB
Manual 2100-694B
Page
22 of 62
TABLE 10
Filter Switch Pressure Settings
0%
10%
0.65
0.70
100%
99.0%
0.40
0.43
100%
99.7%
0.12
0.12
100%
99.3%
0.12
0.12
100%
99.3%
0.40
0.50
100%
98.7%
0.30
0.35
100%
99.8%
FIGURE 33
Dirty Filter Switch and Filter Indicator Light
TUBE LOCATED IN
AIRSTREAM AFTER FILTER
20%
30%
40%
0.75
0.85
0.95
97.0%
96.4%
95.5%
0.45
0.50
0.55
98.7%
96.8%
96.0%
0.12
0.20
0.20
99.4%
98.7%
96.5%
0.12
0.12
0.20
99.4%
98.8%
97.3%
0.60
0.70
0.75
98.1%
97.5%
91.7%
0.40
0.45
0.50
99%
98.5%
96.8%
FILTER
LIGHT
TUBE LOCATED IN
AIRSTREAM BEFORE FILTER
50%
60%
70%
1.05
1.25
1.50
92.7%
88.1%
80.6%
0.65
0.75
0.90
94.4%
91.6%
85.2%
0.35
0.35
0.40
92.1%
91.3%
87.9%
0.20
0.20
0.30
91.5%
89.8%
88.3%
0.80
0.90
1.00
81.3%
79.1%
78.6%
0.65
0.70
0.90
89.9%
84%
82.2%
SCREW TO
REMOVE COVER
COVER
MIS-3901
MIS-3901