Shutting Down For Long Periods; Scheduled Maintenance - Mitsubishi Electric Climaveneta i-BX-004-013M Installation, Operation And Service Manual

Table of Contents

Advertisement

MAINTENANCE AND SERVICE
SYSTEM emergency operation
If the heat pump is not working correctly or the compressor
has shut down, emergency operation can be activated.
Emergency operation involves heating the water using the
electric heaters available on the system (outlet, storage
tank).
The compressor remains off.
To enable manual operation of system heaters, set parame-
ter 0620 = 1 (manual)
DOMESTIC HOT WATER emergency operation
If the heat pump is not working correctly or the compressor
has shut down, emergency operation can be activated.
Emergency operation involves heating the domestic hot
water using the electric heater inside the storage tank.
To enable manual operation of DHW storage heaters, set
parameter 0202 = 2.

SHUTTING DOWN FOR LONG PERIODS

After deactivating the heat pump:
- Disconnect the unit from the power supply.
- Make sure the remote keypad is in the "OFF" position.
- Place QF1 in the OFF position (see wiring diagram).
- Deactivate the indoor terminal units by placing the switch
of each unit in the "OFF" position.
- Close the water valves.
If the outside temperature may fall below zero; there is
the risk of freezing.
The water circuit MUST BE EMPTIED AND CLOSED (if
draining after operation in heat pump mode, beware that

SCHEDULED MAINTENANCE

Never perform any cleaning operations before having
disconnected the unit from the mains power supply.
Make sure power is not connected before proceeding.
Control maintenance is fundamental to maintain the efficiency
of the unit both in terms of operation and energy consumption.
The Technical Service maintenance plan must be observed,
with an annual service which includes the following opera-
tions and checks:
- Filling of the water circuit;
- Presence of air bubbles in the water circuit;
- Efficiency of safety devices;
- Power supply voltage;
- Electrical power input;
- Tightness of electrical and water connections;
Description
Type of outlet electric heater oper-
ation
- SUPPLEMENTARY
- REPLACEMENT
Enable manual heater operation
Set the parameters following the sequence described in
the table
Description
Electric heater operating mode:
- DISABLED
- HEAT PUMP ONLY
- HEATER+HP
- HEATER ONLY
the water may be hot), or antifreeze must be added in
the proportion recommended by the manufacturer.
It is recommended to use non-toxic food grade
antifreeze, compliant with the standards in force in the
countries where the unit is used, if domestic hot water
production is also featured.
If the mains switch is turned to "off" for more than four
hours, after turning it on and before reactivating the unit,
leave the power on but the unit deactivated for at least
two hours to preheat the oil in the compressor sump.
- Condition of the compressor contactor;
- Efficiency of the plate heat exchanger resistor;
- Verification of operating pressure, superheating and sub-
cooling
- Efficiency of the compressor heater
- Cleaning of the finned coil every three months
- Cleaning of the fan grills
- Cleaning of condensate drain pan.
- Cleaning of water filters.
- Checking the ventilation openings on the base are free of
leaves, bushes or anything else that may obstruct air flow.
For units installed near the sea, the intervals between main-
tenance should be halved.
EN i-BX-(Y)_i-BX-N-(Y)
A
Menu
Parameter
Default
UOM
no.
Mn01
010G
REPLACE-
MENT
Mn06
0620
1
Parameter
Value to be
UOM
Menu
no.
set
Mn02
0202
HEATER
ONLY
A
A
75