Mitsubishi Electric Climaveneta i-BX-004-013M Installation, Operation And Service Manual page 71

Table of Contents

Advertisement

SYSTEM CONFIGURATION
System number 3
Parameter configuration
Description
Select system configuration
Enable zone management
NOT = Disabled
YES = Enabled
System type (table 1)
Mixing valve ZONE 1
Type of mixing valve 1= 0-10V
HEATING compensation curve ZONE 1
Enable compensation curve NOT = Disabled YES = Enabled
Heating compensation curve number
Enable room temperature influence
NOT = Disabled YES = Enabled
Room Authority
MINIMUM set point limit for curve
MAXIMUM set point limit for curve
COOLING compensation curve of ZONE 1
Enable compensation curve NOT = Disabled YES = Enabled
Maximum temperature set point limit in cooling mode (Tm1)
Minimum outside temperature corresponding to max. outlet
temperature (Te1)
Minimum temperature set point limit in cooling mode (Tm2)
Maximum outside temperature corresponding to min. outlet
temperature (Te2)
HUMIDITY CONTROL ZONE 1
Enable compensation for room humidity, ZONE LT1
NOT = Disabled YES = Enabled
Room relative humidity value to start increasing water temperature
set point
Maximum outlet temperature hysteresis corresponding to 100%
relative humidity
Enable contact kA11 as DEHUMIDIFIER (The contact closes and the
dehumidifier is activated when the humidity measured by the probe on
the A5 room controller exceeds the value set for parameter 0172)
HEATING compensation curve ZONE 2
Enable compensation curve NOT = Disabled YES = Enabled
Compensation curve number
Enable room temperature influence
NOT = Disabled
YES = Enabled
Room Authority
MINIMUM set point limit curve
MAXIMUM set point limit curve
COOLING compensation curve ZONE 2
Enable compensation curve NOT = Disabled YES = Enabled
Maximum temperature set point limit in cooling mode (Tm1)
Minimum outside temperature corresponding to max.
temperature (Te1)
Minimum temperature set point limit in cooling mode (Tm2)
Maximum outside temperature corresponding to min.
temperature (Te2)
ZONE 2 room controller address setting
Device address setting
Low temperature ZONE LT1 room control unit address setting
High temperature ZONE HT1 room control unit address setting
The SYSTEM compensation curve in HEATING mode, parameter 0159, must be set so as to reach an outlet temperature suitable for the high
temperature zone with radiators. The mixed zone is managed according to the compensation curve set for parameter 0174.
The room unit (A5), supplied as standard with the heat pump, controls the room temperature in zone 1, with radiant panels, the additional room
unit (accessory) controls the room temperature in zone 2, with radiators or fan coils.
Enable contact HL1 as secondary circuit pump:
- RELAY ALARM
- DEHUMIDIFIER
- AT1 PUMP
- SUMMER/WINTER
* obligatory values for the present configuration
Parameter
Menu
Default
no.
Mn01
016A
NOT
Mn01
0101
Mn01
012T
0-10
Mn01
0167
NOT
Mn01
0174
0,7
Mn01
0178
NOT
Mn01
0179
30
Mn01
0180
23
Mn01
0181
45
Mn01
0169
NOT
Mn01
0132
20
Mn01
0133
23
Mn01
0134
18
Mn01
0135
36
Mn01
0171
NOT
Mn01
0172
70
Mn01
0173
15
Mn01
011B
Mn01
0152
NOT
Mn01
0159
Mn01
0163
NOT
Mn01
0164
30
Mn01
0165
30
Mn01
0166
48
Mn01
0154
NOT
Mn01
0128
20
Mn01
0129
23
Mn01
0130
18
Mn01
0131
36
addr
addr
addr
RELAY
Mn01
015A
ALARM
EN i-BX-(Y)_i-BX-N-(Y)
U I A
Write set value
UOM
YES
0
3*
°C
°C
°C
°C
°C
°C
°C
DEHUMIDIFIER
1
°C
°C
°C
°C
°C
°C
1
11*
1
14
1
11
AT1 PUMP
-
-
%
%
-
-
-
%
-
71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents