INSTALLATION
CHOICE OF INSTALLATION SITE
Before installing the unit, agree with the customer the site
where it will be installed, taking the following points into con-
sideration:
• check that the support surface is adequate to support the
weight of the unit;
• respect safety distances between the unit and other equip-
ment or structures so that the fan air intake and outlet are
not blocked in any way.
• Follow the instructions shown in the chapter on DIMEN-
SIONED DRAWINGS to allow room for maintenance oper-
ations.
• Unit for outdoor installation
• Although the noise level produced by the unit during oper-
ation is limited, avoid installation in places where even low
noise levels can cause annoyance (bedroom windows, ter-
races).
• Select a place where the hot air discharged from the unit
does not cause a disturbance.
• The appliance must not be used in potentially explosive
atmospheres.
• The unit must be installed far away from places where
flammable gas leaks may occur.
• In coastal areas or other places exposed to salt spray, cor-
rosion may affect the life of the unit. Avoid direct exposure
to wind from the sea.
If installing multiple units, follow the instructions shown in
Figures 1, 2, 3.
1
If installing a series of units, even on different levels, ensure
the minimum clearances as illustrated in drawing 1 and in
the following table.
Units on different levels (mm)
A
B
1800
600
C
D
400
300
2
If installing one or more units near vertical walls, ensure the
minimum clearance between the units and between unit and
wall, as illustrated in the drawing 2 and in the following
table.
Units in relation to walls (mm)
E
F
900
400
3
If installing units between two vertical walls, the clearances
should be such as to prevent the flow leaving the fans from
interacting with the intake flow, causing continual malfunc-
tioning.
Units between walls (mm)
L
2700
EN i-BX-(Y)_i-BX-N-(Y)
I
G
H
900
400
M
400