Regency ® Direct Vent Flex System - Regency Panorama P33CE Owners & Installation Manual

Zero clearance direct vent gas fireplace
Hide thumbs Also See for Panorama P33CE:
Table of Contents

Advertisement

installation
Regency
Direct Vent Flex System
®
Horizontal Terminations Only
This venting system, in combination with the P33CE Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey/
Intertek. The location of the termination cap must conform to the requirements in the "Exterior Vent Terminal Locations" Section .
Regency
Direct Vent Flex Termination Kit (Part # 946-513) includes all the parts needed to install the P33CE with a maximum run of 2 feet. If install-
®
ing the P33E with a continuous vent length of more than 2 ft (.6m) to a maximum of 10 ft. (3.0m) use Kit # 946-515 (4 ft) or 946-516 (10 ft) or see "Rigid Pipe
Venting Systems" Section for alternate venting arrangements.
1) 6-7/8" dia. flexible liner (2 ft. length)
2) 4" dia. flexible liner (2 ft. length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" drill point,
stainless steel (4)
Notes:
1) Liner sections should be continuous
without any joints or seams.
2) Only Flex pipe purchased from Regency
may be used for Flex installations.
Minimum
Rigid Pipe Center-Line
|
24
P33CE-11 Direct Vent Gas Fireplace
4" (102mm)
dia. flue pipe
®
Minimum
Flex Kit Center-Line
Wall Thimble (2 pc)
(required in
Canada only)
spring
spacer
6-7/8"
(173mm)
dia. Flue pipe
Wherever necessary due to
external location of cap, the
AstroCap can be replaced with
the FPI Riser Vent Termination
Cap or the Dura-Vent Snorkel
Termination Cap.
TM
AstroCap
Termination Cap
(Part# 946-523/P)
See Figure 1 below for
Alternate Caps.
Alternate
Horizontal
Termination
Caps
Figure 1