DRT40 Multi-View Series Direct-Vent Gas Fireplace
Electronic Models - Electronic models have a
fixed rate gas valve. Input of electronic models
is shown in Table 1.
Input (BTU) Gas Valves (all models)
Models
Ignition
Fuel Type
Electronic
ST and PF
Natural
Electronic
CL and CR
Natural
Table 1
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel #
Minimum
4.5" WC
Natural Gas
(1.12 kPa)
11.0" WC
Propane
(2.74 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel #
Low
Natural
(Lo) 2.2" WC
Gas
(0.55 kPa)
(Lo) 6.3" WC
Propane
(1.57 kPa)
Table 3
Test gauge connections are provided on the
front of the electronic gas control valve (identi-
fied IN for the inlet and OUT for the manifold
side). The control valves have a 3/8" (10mm)
NPT thread inlet and outlet side of the valve
(refer to Figure 1).
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
6
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
Input Rate
The appliance must be isolated from the
(BTU / HR)
gas supply piping system by closing its
equipment shutoff valve during any pressure
37,000
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psi
(3.5 kPa).
31,000
Orifice Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard burner
orifice sizes (marked with an "*" in Table 4).
For elevations above 4500 feet, contact your
gas supplier or qualified service technician.
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
Maximum
by either:
10.5" WC
• Using gas that has been derated by the gas
(2.61 kPa)
company.
13.0" WC
• By changing the burner orifice to a smaller
(3.23 kPa)
size as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel Gas
Code NFPA 54/ANSI Z223.1—latest edition or,
in Canada, the CAN/CGA-B149.1 codes—latest
edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
High
in the USA, the National Fuel Gas Code NFPA
(Hi) 3.5" WC
54 / ANSI Z223.1—latest edition or, in Canada,
(0.87 kPa)
the CAN/CGA-B149.1—latest edition.
(Hi) 10.0" WC
Flame breadth, height and width will diminish
(2.49 kPa)
4% for every 1,000 feet of altitude.
Burner Orifice Sizes (all models)*
Model
ST and PF
CL and CR
Table 4
*For elevations of 0-4500 ft. or 0-1372 m
Gas Valve Diagrams
See Figure 1.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Natural
Propane
Gas
Gas
drill size (inches)
drill size (inches)
#32 (0.116")
*
1.65mm (0.065")
*
37L82 •
74L88 •
2.7mm (0.106")
*
1.55mm (0.061")
*
18L40 •
42M79 •
* Standard size installed at factory
• Part /Cat. Number
Installation and Operation Instructions
900299-00, 02/2019
Honeywell Electronic
Figure 1

COMMONWEALTH OF MASSACHUSETTS

REQUIREMENTS
These appliances are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R. Sections 4.00 through 8.00.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The flexible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified..
• A metal or plastic identification plate must
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.