Fig. 1; Safety Precautions; Installation - Jøtul I 350 Installation And Operating Instructions Manual

Hide thumbs Also See for I 350:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 16

3.0 Safety precautions

3.1 Fire preventive measures
Any use of the fireplace may represent some danger. Therefore,
respect the following instructions:
Ensure that furniture and other flammable materials do not
get too close to the fireplace.
Let the fire die. Never put it out with water as this may
damage the product.
The fireplace gets warm when used and may cause burns if
touched.
Ash must be properly disposed of outdoors, or emptied
where it does not entail a fire hazard.
3.2 Air supply
Warning! Please ensure that there is adequate air supply from
the outdoors to the room in which the fireplace is to be installed.
Ensure that air vents in the room where the fireplace is located
are not blocked.
An inadequate air supply could cause smoke gas to escape
into the room. This is very dangerous! Symptoms of this include
smoky smell, drowsiness, nausea and feeling ill.
Avoid using mechanical fan vents in a room with a fireplace.
This may cause negative pressure and draw poisonous gasses
into the room.

4.0 Installation

4.1 Floor
Foundations
Ensure that the floor is strong enough for the fireplace. See
«2.0 Technical data» for weights.
Wooden floor protection
Requirements for the floor plate:
The floor plate must be in accordance with national laws and
regulations. (See Building regulations)
We recommend that you contact the local Jøtul dealer prior to
the installation.
Any flooring made of combustible material, such as linoleum,
carpets, etc. must be removed from under the floor plate.
Requirement for protecting combustible
flooring in front of fireplace
The front plate must be in accordance with national laws and
regulations.
Contact your local building authorities regarding
restrictions and installation requirements.
4.2 Wall
Distance to walls made of combustible material -
see fig. 1
Requirements for insulation
80 mm rock wool 120 kg/m
0.2 mm aluminium.
Distance from the stove to the insulation on the back panel.
See fig. 1 and 2:
Minimum 15 mm.
Distance to walls protected by a firewall-see

fig. 1

Firewall requirement
The firewall must be at least 100 mm thick and be made of
brick, concrete-stone or light concrete. Other materials and
constructions with satisfactory documentation may also be
used.
Distance from the stove to firewall:
The distance must be minimum 15 mm.
Distance to non combustible wall -see fig. 1
A non combustible wall is here mentioned as a non load-bearing
wall of cement /brick.
Requirements for the stove surround
The stove surround must be made in an incombustible material
and be carried out in accordance with the requirements
indicated under section: Safety precautions.
Note that the entire back panel within the surround must be
covered by insulation.
If the stove cowling is bricked up to the ceiling and the ceiling
is made of combustible material, on top of the warming
chamber and the cowling vents an extra ceiling panel must be
installed to avoid heating the ceiling.
For example use:
Rock wool 10 mm thick on top of a steel plate min. 0.9 mm.
Ensure airing out the top of the stove cowling – for example an
opening towards the ceiling, or approx. 5 cm
2A).
Note: Remember that it should be possible to sweep and to
inspect the installation.
4.3 Air supply (fig. 2)
Air should be allowed to flow between the insert and the
brickwork,
and it is very important that there is a free air supply
to the draft catchers on top of and under the insert.
ENGLISH
3
foliated on one side with
2
opening (fig.
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

I 350 fl

Table of Contents